GL6000, GL7000, GL9000, GL11000, WSM
GENERATOR
Circuit Breaker (NFB)
1. Test for continuity between the each upper and lower breaker
terminals with an ohmmeter.
2. Make sure that there is continuity when the breaker switch in
ON
.
3. If there is no continuity, it indicates that the contacts are faulty.
Replace the breaker.
NOTE
• When there is a short-circuit in the wiring, the circuit breaker
trips off. If this happens, eliminate the cause, then reset the
circuit breaker. If the circuit breaker holds, test the load for
faults.
W1022525
(1) Circuit Breaker
[A] GL6000, GL7000
[B] GL9000, GL11000