2-S2
GL6000, GL7000, GL9000, GL11000, WSM
GENERATOR
Generator
Trouble
Checking Method
Measurement
Operating
Condition
Possible Cause
Countermeasure
Voltmeter Indicates
Normal Voltage But
no Output Voltage is
Delivered.
Measure the
voltage at the
output terminal
using a voltmeter.
(250V at AC range)
Output voltage is
0 V.
Circuit breaker is
OFF
Set the circuit
breaker to ON. If
it goes OFF again,
check the cause
(overload, short
circuit, etc.).
Set the circuit
breaker to ON
after removing the
cause.
Improper contact of
output terminal or
receptacle
Repair or replace
Improper contact of
the NFB wiring part
(inside the control
box)
Check wiring and
repair
Defective NFB
Replace
Disconnected wiring
harness (inside the
control box)
Check wiring and
repair
Voltmeter Does not
Indicate Any Voltage
and Also Output
Voltage is not
Delivered
Measure the
voltage at the
output terminal
using a voltmeter.
(250V at AC range)
Output voltage is
0 V.
Disconnected stator
coil
Repair or replace
Lack of residual
magnetism
Replace rotor
Only slight output
voltage is delivered
Excessive wear of
brush or improper
contact of it
Replace brush
and clean the
contact surface of
it
Disconnected rotor
coil
Repair or replace
Defective A.V.R.
Replace
Improper contact of
the connector for
A.V.R. & stator
Check and repair
Excessive wear of
brush or improper
contact of it
Replace brush
and clean the
contact surface of
it
Breaker Trips OFF
Measure the
voltage at the
output terminal
using a voltmeter.
(250V at AC range)
Output voltage is
normal
Abnormality of
loading circuit
Locate the cause
(short-circuit, or
overload, etc.)
and remove
KiSC issued 05, 2015 A