Dok. Nr. R60744_Index 1a
Page 16 / 27
5.7.
Master PIN and User PIN
The SMCB.1 has two password levels. The device is shipped with factory set values
Master PIN = 0000 and User PIN = 0000 and is therefore not password protected. Full
access to all functions is possible. However, the SMCB.1 control unit can be protected
against unauthorized access by selecting a PIN specification not equal to 0000.
Both parameters can be changed in the menu "Unit Settings"
Display Unit
Edit Data
Unit Settings
Master PIN
Display Unit
Edit Data
Unit Settings
User PIN
You can enter a 4‐digit PIN code of your choice. After confirming with OK, the change
must still be saved (see chapter 5.6) so that next time the SMCB.1 control unit is
protected by a PIN code.
When using a "User PIN", a "Master PIN" should always be assigned too
so that access to the SMCB.1 parameters is retained.
5.7.1.
Master PIN
When using the "Master PIN", the user can access all functions and parameters in the
safety and operating device by entering the PIN code.
5.7.2.
User PIN
When using the "User PIN", the user can only load the data stored in the operating unit
of the safety device by entering the PIN code and transfer it to the safety device. Any
editing of the parameters in the safety and operating device is blocked.
Only following menu items are available:
To load the parameters for a safety device from the flash
memory of the SMCB.1, select "Load Data from Display
Memory" and
confirm with OK
.
To save the parameter set in the safety device, select "Save
Data To Safety Unit" and confirm with OK.