39
Insulation
Resistance Fail
F05
(1)
Check for good ground connection.;
(2)
Check if the earth resistance of PV+ and PV-
is greater than 2M
Ω
;
(3)
If it is smaller than 2M
Ω
, check PV string for
ground fault or poor ground insulation; if it is
greater than 2M
Ω
, please contact the local
inverter customer service once fault is not
removed.
Relay Fail
F07
F08
(1) Restart the inverter and wait until it functions
normally.
(2) Contact customer service if error warning
continues.
GFCI Sensor
Fail
F09
(1) Restart the inverter and wait until it functions
normally.
(2) Contact customer service if error warning
continues.
Current Sensor
Fail
F10
(1) Restart the inverter and wait until it functions
normally. (2) Contact customer service if error
warning continues.
PV Input
Short
F11
(1) Restart the inverter and wait until it functions
normally. (2) Contact customer service if error
warning continues.
Communication
Fault
F32
(1) Restart the inverter and wait until it functions
normally. (2) Contact customer service if error
warning continues.
Overload
Warning
W01
(1)
Wait five minutes for the inverter to restart;
(2) Check whether the load is in compliance with
the specification;
(3) Contact customer service if error warning
continues.
Bat Volt Open
W02
(1) Battery is not connected;
(2) Check if battery wiring port is short circuited;
(3) Contact customer service if error warning
continues.
Bat Volt
Under
W03
(1) Check the battery availability;
(2) Contact customer service if error warning
continues.