Chapter 6 Operation and Maintenance 59
Foc u sA ir I n - ro w Ai r Con d iti on e r U s er ´s M an u a l
6.7 Wet Film Humidification Maintenance (Optional)
6.7.1 Replacing wet film
(1) Open the rear door and reach out to loosen the captive screws on the wet film module, as shown in Fig. 6-7-1;
(2) Loosen the hose clamp connected to the water supply pipe on the wet film, lift the wet film up and pull it out
as shown in Fig. 6-7-2, and replace it.
Item
Description
❶
Captive screw
❷
Wet film humidifier
Fig. 6-7-1 Loosening the screws
Note
Before replacing the wet film, make sure that the unit is powered off or shut down to prevent entering the
humidification mode during the process of replacing the wet film and causing the wet film inlet pipe to spray
water.