06 Chapter 1 Product Overview
Foc u sA ir P r ec i sio n A ir C on d it ion er U s er ´s Man u al
Item
Requirements
Altitude
<1000m, please consult our technicians when exceed 1000m
Operating
voltage
range
380V±10
%
, 50/60±2Hz
Inlet water
requirements for
humidification
Inlet water quality: Clean tap water;
Inlet water temperature: 4~40℃;
Inlet water pressure: 0.1~0.7Mpa.
[Note: The electrode humidifier cannot use deionized water or distilled water.
Conductivity: 350~750μs/cm]
1.4.2 Storage
The storage environment of in-row air conditioners should meet the requirements of GB4798.1-2019. See
Table 1-4-2 for details.
Table 1-4-2 Storage environment requirements
Item
Requirements
Storage environment
Indoor, clean (no dust, etc.)
Ambient humidity
5
%
RH~95
%
RH (non-condensing)
Ambient temperature
-40℃~+70℃
Storage time
The total transportation and storage time should not exceed 6 months. The
performance needs to be re-calibrated after 6 months