52 Chapter 6 Operation and Maintenance
Foc u sA ir I n - ro w Ai r Con d iti on e r U s er ´s M an u a l
(1) Off-line maintenance: open the rear door, remove the filter, and cut off the power supply of the air
conditioner;
(2) Pull out the plug-in terminals of the fan’s power cord and signal line and cut off the cable ties
corresponding to the fan’s wiring harness to facilitate the following operations;
(3) Loosen the screws of the fan fixing frame with a Phillips screwdriver and take out the fan assembly;
Item Description
❶
Fan power cord terminal
❷
Fan signal line terminal
❸
Fan fixing frame screw
❹
Limit point of fan guard