20 Chapter 2 Mechanical Installation
Foc u sA ir P r ec i sio n A ir C on d it ion er U s er ´s Man u al
2.5
Installing Unit Pipeline
2.5.1
Content of pipeline connection
1.
Connecting copper pipe between the indoor unit and outdoor unit;
2.
Condensate drain pipe;
3.
Humidification water supply pipe (model with humidification);
2.5.2
Physical interfaces
Table 2-5-1 Physical interfaces of indoor unit of air conditioner
Name
Specifications of reserved interface
FS012
,
300mm wide
FS025/030, 300mm
wide
FS025/FS040/050/060/070,
600mm
wide
FS060/070, 600mm
wide
Refrigerant
liquid pipe
3/4 inch
15.88mm
15.88mm
19.05mm
Refrigerant
gas pipe
7/8 inch
19.05mm
19.05mm
22.00mm
Humidification
inlet pipe
G3/4 inch external thread
Gravity drain
pipe
ID15*OD22mm
Water pump
drain pipe
ID10*OD16mm
Table 2-5-2 Physical interfaces of outdoor unit of air conditioner
Name
Specifications of reserved interface
KCS018
KCS032/036/042
KCS048/054/062/72
KCS084/096
Refrigerant
liquid pipe
5/8 inch
15.88mm
15.88mm
19.05mm
Refrigerant
gas pipe
3/4 inch
19.05mm
22.22mm
25.4mm
Table 2-5-3 Physical interfaces of cryogenic components
Name
Specifications of reserved interface
DW-07
DW-14
Refrigerant liquid
pipe
7/8-14UNF
stop valve (5/8’)
19.05mm (welded)
Table 2-5-4 Physical interface of energy-saving module
Содержание FocusAir ESM022