9 Trouble-shooting
55 of 68
Hyamat SVP Eco
9.2 Trouble-shooting: frequency inverter
WARNING
Improper work to remedy faults
Risk of injury!
▷
For any work performed to remedy faults, observe the relevant information
given in this instruction manual and/or in the product literature provided by the
accessories manufacturer.
If problems occur that are not described in the following table, consultation with the
KSB service is required.
A
Mains fuse rating too small for the nominal mains current.
B
Motor does not start.
C
Motor running unevenly.
D
Max. speed not reached.
E
Motor running at maximum speed only.
F
Motor running at minimum speed only.
G
No/faulty 24 V supply.
H
Wrong direction of rotation of the motor.
I
Fault message/protective tripping.
Table 36:
Trouble-shooting
A B C D E
F G H
I Possible cause
Remedy
-
✘
-
-
-
-
✘
-
- No voltage
Check the mains voltage; check the mains fuses.
-
✘
-
-
-
-
-
-
- No enable
Check enable via DIGIN-EN and system start.
✘
-
-
-
-
-
-
-
- Mains fuse rating too small for
frequency inverter input
current
Check configuration/selection of mains fuse.
-
-
-
✘
-
-
-
-
- No setpoint signal or setpoint
set too low / drive overloaded
and in i
2
t control mode
Check setpoint signal and operating point.
-
-
-
-
✘
-
-
-
- Process-related persistent
control deviation (actual value
smaller than setpoint) or no
actual value (e.g. due to
broken wire)
Check setpoint signal/actual value signal. Check
operating point. Check controller setting.
-
✘
-
-
-
-
-
-
-
✘
Permissible voltage range
undershot/exceeded
Check mains voltage; supply frequency inverter with
required voltage.
-
-
-
-
-
-
-
✘
- Wrong direction of rotation
setting
Change the direction of rotation.
-
-
✘ ✘
-
-
-
-
✘
Frequency inverter overloaded Reduce the power input by lowering the speed;
check the motor/pump for blockages.
-
✘
-
-
-
-
-
-
✘
Short circuit in control cable/
pump blocked
Check/replace control cable connections. Remove the
blockage manually.