7 Operation
42 of 68
Hyamat SVP Eco
7.2.1.2.1 Menu: Operation
The Operation section contains all information required for operating the machine
and the process. This includes:
▪
Login to device with password
▪
Operating and measured values for motor, frequency inverter, pump and system
▪
Setpoints and control values
▪
Energy meter and operating hours
7.2.1.2.1.1 Access levels
Three access levels have been defined to prevent unintentional or unauthorised
access to frequency inverter parameters:
Table 25:
Access levels
Access level
Description
Standard (No Login)
Access without password entry.
Customer
Access level for the expert user with access to all parameters required for
commissioning
Customer service
Access level for service personnel.
If a parameter's access level is not explicitly specified, the parameter is always
assigned the customer access level.
Table 26:
Access level parameters
Parameter Description
Possible settings
Factory setting
1-1-1
Customer Login
Log in as customer
0000...9999
0000
1-1-2
Service Login
Log in for access to special parameters for KSB
Service
0000...9999
-
1-1-4
Logout
Log out of all access levels
Run
-
NOTE
If no keys are pressed for ten minutes, the system will automatically return to the
standard access level.
The password can be changed after entering the factory default password.
Table 27:
Parameters for changing passwords
Parameter Description
Possible settings
Factory setting
1-1-5
Customer Access ID
Changing the customer access ID
0000...9999
-
1-1-6
Service Access ID
Changing the service access ID
0000...9999
-
7.2.1.2.1.2 Operating values for input and output signals
The status of the digital inputs/relay outputs is displayed via the Digital Inputs
(
1-2-4-6
) and Digital Outputs (
1-2-4-7
) parameters.
Table 28:
Example of status of digital inputs (1-2-4-6). 24 V is applied to digital input 1: System Start
Optional IO card
Standard
Digital input
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
Bit pattern on display
0
0
0
0
0
0
0
I