7 Operation
33 of 68
Hyamat SVP Eco
Table 15:
Assignment of keys for manual mode
Key
Function
MAN
MAN operating key:
▪
When switching the operating mode from AUTO to MAN, the current operating speed is
used as control value (Manual)
1-3-4
and is displayed accordingly. The control point
1-3-10
must be set to Local.
▪
When switching the operating mode from OFF to MAN, the frequency inverter operates
at minimum speed. The control point
1-3-10
must be set to Local.
▪
If the control value (Manual)
1-3-4
is defined via an analog input, the analog input speed
is accepted.
Arrow keys:
▪
Pressing the arrow keys changes and immediately accepts the control value (Manual)
1-3-5
. Making a change using the arrow key has a direct effect even when not confirmed
with OK. The speed can only be changed between the set minimum speed and the
maximum speed.
ESC
OK
ESC/OK key:
▪
Press the OK or ESC key to go from digit to digit. Press the ESC key to go back. Changes
are rejected. Pressing the OK key for the right-hand digit takes you back to the main
screen.