10 Related Documents
78
of
92
KSB Delta Macro
1983.843/04-EN
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-7-2-3
Tank level
-
-
Everybody
Nobody
-
2-7-2-3-1
Start level for rainwater tank
filling
Start tank filling level drinking water
… stop tank filling level rainwater
0,6
Everybody
Service
-
2-7-2-3-2
Stop level for rainwater tank
filling
Start tank filling level rainwater …
high-water level
1
Everybody
Service
-
10.2.2.8 Control algorithms
Table 36:
Control algorithms parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-8
Control algorithms
-
-
Service
Nobody
-
2-8-1
PID controller
-
-
-
-
-
2-8-1-1
Proportional constant
Value range according to controller
5
Service
Service
-
2-8-1-2
Integral constant
Value range according to controller
0
Service
Service
-
2-8-1-3
Differential constant
Value range according to controller
0
Service
Service
-
2-8-2
Input signals
-
-
Service
Nobody
-
2-8-2-1
Damping factor
Value range according to controller
TBD
Service
Service
-
2-8-3
System start-up time delay
-
-
-
-
-
2-8-3-1
System start-up time delay
0 … 60 s
10 s
Service
Service
-
2-8-4
Multi-pump operation
-
-
-
-
-
2-8-4-1
Start flow rate
0 .. 100 %
0,95
Service
Service
-
2-8-4-2
Speed on percent
0 .. 140 %
1
Service
Service
-
2-8-4-3
Speed off percent
0 .. 90 %
0,5
Service
Service
-
2-8-4-4
Pump dynamic control
1 .. 100 %
0,3
Service
Service
-
10.2.2.9 Display
Table 37:
Display parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-10
Access
-
-
Everybody
Nobody
-
2-10-1
Display
-
-
Everybody
Nobody
-