Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-5-3-2-4
Response
Message
Message
Everybody
Service
-
Flushing
2-5-3-3
Water stagnation monitoring
-
-
-
-
-
2-5-3-3-1
Water stagnation monitoring
Disabled
Disabled
Everybody
Service
-
Enabled
2-5-3-3-2
Source
Flow sensor
-
Everybody
Service
-
Flow switch
Flow estimation (VFD)
2-5-3-3-3
Time of stagnation
0 … 7 d
24 h
Everybody
Service
-
2-5-3-3-4
Response
Message
Message
Everybody
Service
-
Flushing with check run
2-5-3-4
Forced flushing
-
-
-
-
-
2-5-3-4-1
Forced flushing
Disabled
Disabled
Everybody
Service
-
Enabled
2-5-3-5
Flushing function
-
-
Everybody
Nobody
-
2-5-3-5-2
Minimum flushing time
0 … maximum flushing time
10 s
Everybody
Service
-
2-5-3-5-3
Maximum flushing time
Minimum flushing time … 999 s
60 s
Everybody
Service
-
2-5-3-5-4
Maximum flushing attempts in
24 hours
0 … 10
5
Everybody
Service
-
2-5-3-5-5
Stop temperature for flushing
0 … maximum temperature
20 °C
Everybody
Service
-
2-5-3-5-6
Flushing time for each pump
0 … 999 s
10 s
Everybody
Service
-
2-5-4
Emergency power operation
-
-
Everybody
Nobody
-
2-5-4-2
Maximum system load
1 … maximum number of pumps
1
Everybody
Service
-
2-5-4-3
Stop delay enabled/disabled
Disabled
Enabled
Everybody
Service
-
Enabled
2-5-5
Discharge pressure monitoring
-
-
Everybody
Nobody
-
2-5-5-1
High pressure alarm
-
-
Everybody
Nobody
-
2-5-5-1-1
Maximum discharge pressure
0 … maximum pump head
Maximum pump
discharge head
Everybody
Service
-
2-5-5-1-2
Delay time
0 … 60 s
10 s
Everybody
Service
-
2-5-5-1-3
Selection of pump response
Message
Message
Everybody
Service
-
Message and stop all pumps
2-5-5-2
Low pressure alarm
-
-
Everybody
Nobody
-