![KSB Delta Macro F Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/ksb/delta-macro-f/delta-macro-f_installation-and-operating-manual_2006597056.webp)
10 Related Documents
56
of
92
KSB Delta Macro
1983.843/04-EN
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1-1-3-2
Number of base load pumps
1 … (number of pumps - number of
peak-load pumps) if pump groups =
base-load and peak-load pump control
1 … (number of pumps - number of
jockey pumps) if pump groups = jockey-
pump control
Number of pumps
Everybody
Nobody
Y
1-1-3-3
Number of peak load pumps
0 … (number of pumps - number of
base load pumps)
0
Everybody
Service
Y
1-1-4
Maximum system load
-
-
Everybody
Nobody
-
1-1-4-1
Maximum number of pumps
0 … number of all pumps
Number of all
pumps
Everybody
Service
-
1-1-5
Manual-0-automatic mode
-
-
-
-
-
1-1-5-1
Manual-0-automatic mode of
pumps
Internal via display
Internal via display Everybody
Service
-
External switches
1-1-6
Fire alarm
-
-
-
-
-
1-1-6-1
Fire alarm mode
Disabled
Disabled
Everybody
Service
-
Enabled
1-1-7
External On/Off
-
-
-
-
-
1-1-7-1
External On/Off mode
Disabled
Disabled
Everybody
Service
-
Enabled
1-1-8
Membrane rupture detection
-
-
-
-
-
1-1-8-1
Membrane rupture detection
Disabled
Disabled
Everybody
Service
-
Enabled
1-1-8-2
Digital input
-
-
Everybody
Nobody
-
1-1-8-3
Source
Water detection integrated
Water-detection
on-board
Everybody
Service
-
Membrane rupture detection by
external device
1-1-8-4
Delay time membrane rupture
detection
0 … 99 s
10 s
Everybody
Service
-
1-1-8-5
Delay time reset
0 … 99 s
2 s
Everybody
Service
-