9 Trouble-shooting
52 of 92
KSB Delta Macro
1983.843/04-EN
A B C D E
F G H
I Possible cause
Remedy
-
-
✘ ✘
-
-
-
-
✘
Temperature of power
electronics or stator winding
too high
Reduce the ambient temperature.
▪
Improve ventilation.
▪
Clean cooling fins.
▪
Ensure that the intake opening for the fans is
not blocked.
▪
Ensure that the fans are working properly.
▪
Reduce the power input by changing the
operating point (system-specific).
▪
Check the permissible load and, if necessary, use
external cooling.
-
-
-
-
-
-
✘
-
✘
24 V supply overloaded
Disconnect frequency inverter from the power
supply and eliminate the cause of the overload.
-
-
-
-
-
-
-
-
✘
Dry running
Check the hydraulic system and rectify the fault on
the frequency inverter.
-
-
-
✘
-
✘
-
-
✘
Sensor signal error (e.g.
broken wire)
Check sensor and sensor cable.
-
✘ ✘
-
-
-
-
-
✘
Phase failure (drive)
Check motor connection and stator winding.