10 Related Documents
KSB Delta Macro
73
of
92
1983.843/04-EN
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-5-1-2-1
Additional source
Flow switch
None
Everybody
Service
-
2-5-1-2-2
Delay time for system stop
0 … 99 s
10 s
Everybody
Service
-
2-5-1-2-3
Delay time reset
0 … 99 s
2 s
Everybody
Service
-
2-5-1-3
Pressure sensor on suction side
-
-
Everybody
Nobody
-
2-5-1-3-1
Minimum suction-side pressure
for system stop
0 … maximum pressure sensor range
1 bar
Everybody
Service
-
2-5-1-3-2
Minimum suction-side pressure
for reset
Minimum suction-side pressure for stop
… Maximum pressure sensor range
1.5 bar
Everybody
Service
-
2-5-1-6
Flow switch
-
-
-
-
-
2-5-1-6-2
Discharge pressure deviation
0 …10 bar
1 bar
Everybody
Service
-
2-5-2
Leakage detection
-
-
-
-
-
2-5-2-1
Leakage detection
Disabled
Disabled
Everybody
Service
-
Enabled
2-5-2-2
Source
Water detection integrated
Water-detection
on-board
Everybody
Service
-
Leakage-detection by external device
2-5-2-4
Position
Leakage of pump system
Leakage of pump-
system
Everybody
Service
-
Overflow of tank
2-5-2-5
Response
Message only
Message only
Everybody
Service
-
Message and stop all pumps
Message and close inlet valve
Message, close inlet valve and stop
pumps
2-5-2-6
Delay time leakage detection
0 … 99 s
10 s
Everybody
Service
-
2-5-2-7
Delay time reset
0 … 99 s
2 s
Everybody
Service
-
2-5-3
Hygienic functions
-
-
-
-
-
2-5-3-1
General
-
-
-
-
-
2-5-3-1-1
Hygienic functions
Disabled
Disabled
Everybody
Service
-
Enabled
2-5-3-2
Temperature monitoring
-
-
-
-
-
2-5-3-2-1
Temperature monitoring
Disabled
Disabled
Everybody
Service
-
Enabled
2-5-3-2-2
Maximum temperature
0 … 70 °C
25 °C
Everybody
Service
-
2-5-3-2-3
Minimum temperature
0 … 70 °C
5 °C
Everybody
Service
-