CAUTION
Improper storage
Damage to the power cables!
▷
Support the power cables at the cable entry to prevent permanent
deformation.
▷
Only remove the protective caps from the power cables at the time of
installation.
9.
Do not disconnect the pump set from the hook of the hoisting tackle to prevent
the pump set from tipping over.
10. Clean the pump set (e.g. with water).
11. Collect and properly dispose of any cleaning liquid.
7.2.2.2
Checking the power cables
When removing the pump set from the discharge tube check the power cables for
any damage. Replace any damaged components by original spare parts.
7.2.2.3
Checking the mechanical seal leakage
WARNING
Fluids handled, consumables and operating supplies which are hot or pose a health
hazard
Hazard to persons and the environment!
▷
Collect and properly dispose of the flushing medium and of any residues of the
fluid handled.
▷
Wear safety clothing and a protective mask, if required.
▷
Observe all legal regulations on the disposal of fluids posing a health hazard.
WARNING
Excess pressure inside the pump set
Risk of personal injury when opening the pump set!
▷
Be careful when opening the inner chambers.
NOTE
Slight wear of the mechanical seal is unavoidable. This will be aggravated by
abrasive substances contained in the fluid handled.
Checking the leakage chamber serves to assess the function of the drive-end
mechanical seal.
1
Fig. 12: Checking the leakage chamber
✓
A suitable container for the leakage is on hand.
✓
The pump is positioned horizontally on a level surface and is protected against
rolling off.
7 Servicing/Maintenance
34 of 68
Amacan P