22
6�5� HEATING LOOPS WITH THE KT-1 OR KT-2A THERMOSTATS
Note
During the commisioning process set one KT-1 or KT-2A for each heating loop�
Heating loop
Menu
Parameter name Parameter value range
Note
Heating loop
operational
mode
ON – Turn on
AUTO – Working schedule
OFF – Turn off
Desired
ambient
temperature
+17 °C/+27 °C
Set the desired ambient temperature on which basis
the KSM regulator calculates the right water tempe-
rature in the heating loop.
ECO ambient
mode
–10 °C/+10 °C
ECO lowering the ambient temperature by the set
value.
COMFORT
ambient mode
–10 °C/+10 °C
COMFORT raising the ambient temperature by the
set value.
Setting the
schedule
1–7 days
0 − 24 h
Weekly operational schedule.
Weather mode
−15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning.
Heating curve setting at -15°C ambient temperature.
Weather mode
+15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning
Heating curve setting at +15°C ambient temperature.
Note
If adaptive regulation is turned off, the KSM regulator calculates the temperature of the water in the heating
loop based on the heating curve with reference temperatures at −15 °C and +15 °C�
For a constant water temperature in the heating system set the setting at -15°C and at +15°C to the same value�
Operating instructions
ADAPT System
17-19-45-6702-02