26
6�10� CIRCULATING DHW
Circulating DHW
Menu
Parameter name Parameter value range
Note
Setting the
schedule
1–7 days
0–24 h
The schedule allows up to 6 temperature transitions
per day.
6�10�1� SETTING THE SCHEDULE FOR CIRCULATING DHW
The schedule allows up to 6 room or water temperature transitions per day, every day of the week.
Menu
Weekly overview
Choose settings
Settings
Operational mode
Schedule
Choose day
Edit
Setting interval
Turn on circulation in
NORMAL mode.
Copyj
Turn off circulation.
Paste
Delete
6�10�2� SETTING ANTI-LEGIONELLA HEATING
Setting and activating a function requires 3 parameters:
Menu
Parameter name Parameter value range
Note
Temperature of
anti-Legionella
heating
60–75 °C
Water at a temperature of 75°C eliminates Legionella
in 10 minutes, while water at 60°C eliminates it in 25
minutes.
Interval
0–99 days
Activate the function by entering the heating period.
Turn the function off by setting the heating period
from 24 to 0.
Beginning of
heating
00:00–24:00
Changing the start time sets the beginning of
heating.