FCU 500, FCU 505 · Edition 02.17
90
Parameters
12 .4 .8 Air flow monitoring during post-purge
Parameter 38
Parameter 38 defines whether post-purge takes place
with or without air flow monitoring. Air flow monitoring
during the post-purge time can only be selected if it has
also been activated for pre-purge (parameter 15 or pa-
rameter 35).
Parameter 38 = 0: ON; control element to maximum
capacity.
The actuator is moved to the position for maximum ca-
pacity during the post-purge time. The air flow is moni-
tored.
Parameter 38 = 1: OFF; control element to maximum
capacity.
The actuator is moved to the position for maximum
capacity during the post-purge time. The air flow is not
monitored.
Parameter 38 = 2: OFF; control element to ignition ca-
pacity.
The actuator is moved to the position for ignition ca-
pacity during the post-purge time. If the position of the
actuator at this time is less than the position for ignition
capacity, this position is not changed. The air flow is not
monitored.
Parameter 38 = 3: OFF; control element controller en-
able.
The controller enable signal (terminal 56) is issued. The
position of the actuator can be changed using an exter-
nal temperature controller (controlled cooling). The air
flow is not monitored.