FCU 500, FCU 505 · Edition 02.17
77
Parameters
Name
Parameter
Value range
Description
Factory default settings
69
0
1
2
3
4
5
6
Off
Feedback of position for maximum
capacity (IC 40/RBW)
AND with emergency stop (trm. 46)
AND with air min. (trm. 47)
AND with air flow monitoring (trm. 48)
AND with gas min. (trm. 49)
AND with gas max. (trm. 50)
0
70
0
1
2
3
4
5
6
Off
Reduced DG test duration
AND with emergency stop (trm. 46)
AND with air min. (trm. 47)
AND with air flow monitoring (trm. 48)
AND with gas min. (trm. 49)
AND with gas max. (trm. 50)
0
71
0
1
2
3
4
5
6
7
Off
FCU as zone control unit
External HT signal
AND with emergency stop (trm. 46)
AND with air min. (trm. 47)
AND with air flow monitoring (trm. 48)
AND with gas min. (trm. 49)
AND with gas max. (trm. 50)
0
72
0
1
2
3
4
5
6
7
Off
BCU ready; if not, safety shut-down
BCU ready; if not, fault lock-out
AND with emergency stop (trm. 46)
AND with air min. (trm. 47)
AND with air flow monitoring (trm. 48)
AND with gas min. (trm. 49)
AND with gas max. (trm. 50)
2
73
0
1
2
3
4
5
6
Off
Contactor feedback
AND with emergency stop (trm. 46)
AND with air min. (trm. 47)
AND with air flow monitoring (trm. 48)
AND with gas min. (trm. 49)
AND with gas max. (trm. 50)
0
▼