A11.2 Application Assistant - Saturated Steam
A11.3 Application Assistant - Superheated Steam
Function
Setting / Description
.1
.2 Units
Same options as in A11.1.2.
.3 Process
.3.1 Fluid
Select "Steam".
.3.2 Medium
Select "Saturated Steam".
.3.3 Time Constant
0...100 s
.3.4 Low Flow Cutoff
Enter low flow cutoff point in current volume flow unit.
.4 Current Input
.4.1 Function
Select "On" if applicable.
.4.2 Current Input Meas.
Select "Temperature External" if "Function = On".
.5.1 Temp. Source1
Internal / External / External HART / Not Available
.5.2 Temp. Source2
Internal / External / External HART / Not Available
Temperature source 1 and 2 must be different.
.6 Operating Values
Same options as in A11.1.4.
.7 Current Output
Same options as in A11.1.5.
.8 Binary Output
Same options as in A11.1.6.
.9 Pulse Output
Same options as in A11.1.7.
.10 Frequency Output
Same options as in A11.1.8.
.11 Status Output
Same options as in A11.1.9.
.12 Limit Switch
Same options as in A11.1.10.
.13 Flow Totalizer
Same options as in A11.1.11.
.14 Energy Totalizer
Same options as in A11.1.12.
.15 1. Meas. Page
Same options as in A11.1.13.
.16 2. Meas. Page
Same options as in A11.1.14.
Table 6-23: A11.2 Application Assistant - Saturated Steam
Function
Setting / Description
This application assistant is available if meter type is set to "Heat & Dens. by Pres." or "Heat & Dens. & FAD" (refer to
"C6.3 Extras").
.1
.2 Units
Same options as in A11.1.2.
.3 Process
.3.1 Fluid
Select "Steam".
.3.2 Medium
Select "Superheated Steam".
.3.3 Time Constant
0...100 s
.3.4 Low Flow Cutoff
Enter low flow cutoff point in current volume flow unit.
.4 Current Input
.4.1 Function
Select "On", if applicable.
.4.2 Current Input Meas.
Select "Temperature External" or "Pressure External".
.5.1 Temp. Source1
Internal / External / External HART / Not Available