OPERATION
6
67
OPTISWIRL 2100
www.krohne.com
04/2020 - 4007600701 - MA OPTISWIRL 2100 R01 en
C5.3.2 Measurement 1. Line
Select: Volume Flow / Norm. Volume Flow / Mass Flow / Volume / Norm. Volume /
Mass / Density / Vortex Frequency / Velocity / Reynolds Number
C5.3.3 0% Range
The set value represents the 0% point of the bargraph indication.
Usually 0% flow = 4 mA, but it is also possible to define a higher flow value for 4 mA.
This menu is only avaible, if an option containing a bargraph was selected in C5.3.1.
C5.3.4 100% Range
The set value represents the 100% point of the bargraph indication.
Usually 100% flow = 20 mA, but it is also possible to define a lower flow value for 20 mA.
This menu is only avaible, if an option containing a bargraph was selected in C5.3.1.
C5.3.5 Format 1. Line
Automatic or 1...8 digits
C5.3.6 Measurement 2. Line
Same as C5.3.2, visible if more than one value was selected in C5.3.1.
C5.3.7 Format 2. Line
Same as C5.3.5, visible if more than one value was selected in C5.3.1.
C5.3.8 Measurement 3. Line
Same as C5.3.2, visible if three values were selected in C5.3.1.
C5.3.9 Format 3. Line
Same as C5.3.5, visible if three values were selected in C5.3.1.
Table 6-27: Menu description C5
Function
Setting / Description
C6 Device
C6.1 Information
C6.1.1 Tag
Entry and display of measuring point identifier (8 digits).
C6.1.2 Long Tag
Entry and display of long measuring point identifier (1...32 digits).
Entry will be displayed in the header bar on the LC display (depending on letter size,
min. 11 digits can be displayed).
C6.1.4 Serial Number
Individual device ID (read-only).
C6.1.5 Manufacturer ID
HART
®
Manufacturer ID = 00069 (0x45) [KROHNE] (read-only)
C6.1.6 Device Name
Optiswirl 2100 (read-only)
C6.1.7 V Number
Internal order number (read-only).
C6.1.8 Electronic Revision
Electronic revision of this device as listed on device nameplate (for details refer to
Software history
on page 6).
C6.1.9 Device Revision
(read-only)
C6.1.10 Software Revision
(read-only)
C6.1.11 Hardware Revision
(read-only)
C6.1.12 Electronic Serial No.
Individual ID of electronics component (read-only).
C6.1.13 CG Number
Article code for signal converter hardware (read-only).
C6.1.14 Production Date
(read-only)
C6.1.15 Calibration Date
(read-only)
C6.2 Security
C6.2.1 Login
Enter four digit password to gain a specific access level (for details refer to
Security
and permissions
on page 50).
C6.2.2 Change Password
Change the password associated to the access level currently active.
C6.2.3 Reset Passwords
Reset all passwords to their default setting (for details refer to
Security and
permissions
on page 50).
C6.4 Errors
Function
Setting / Description
C5 Display