C3.1.3 Device Information
Informative text can be added to describe the device in the HART
®
communication loop.
C3.1.3.1 Descriptor
Commenting text to label instrument can be added; 1
…
16 digits.
C3.1.3.2 Message
Here additional information can be added.
C3.1.3.3 Date
Customer-defined date can be set here.
C3.1.3.4 Cfg. Change Counter
Counter for changes in settings (read-only).
C3.1.4 HART Variables
Definition of HART
®
variables.
C3.1.4.1 Current Out. Meas.
Primary HART
®
variable; identical with current output measurement variable.
C3.1.4.4 Quaternary HART
Select (availibility depending on fluid and medium configuration): Volume Flow / Norm.
Volume Flow / Mass Flow / Volume / Norm. Volume / Density / Vortex Frequency /
Velocity / Reynolds Number
Table 6-25: Menu description C3
Function
Setting / Description
C4 Totalizer
C4.1 Flow Totalizer
C4.1.1 Measurement
Select: Volume Flow / Norm. Volume Flow / Mass Flow
"Norm. Vol." is only available if fluid is "Gas".
C4.1.2 Preset Value
Set value, which triggers event "Flow Totalizer Overflow" (for details refer to
Status
messages and diagnostic information
on page 69).
C4.1.3 Reset Totalizer?
Select: Yes / No
C4.1.4 Set Start Value
Set start value in selected unit.
Start value has to be confirmed with "Yes" or refused with "No".
C4.1.5 Start Totalizer?
Select: Yes / No
C4.1.6 Stop Totalizer?
Select: Yes / No
C4.1.7 Information
Display of current totalizer values.
The menus C4.1.7.1 to C4.1.7.3 are available depending on selected measurement
variable in C4.1.1.
C4.1.7.1 Volume
Display of current totalizer value for volume flow.
C4.1.7.2 Norm. Volume
Display of current totalizer value for norm. volume flow.
C4.1.7.3 Mass
Display of current totalizer value for mass flow.
Table 6-26: Menu description C4
Function
Setting / Description
C5 Display
C5.1 Language
Available display languages: German, English, French, Italian, Spanish, Russian,
Chinese, Swedish, Danish, Czech, Polish, Turkish, Slovenian;
13 further languages in preparation (for details refer to
Menu languages
on page 52)
C5.2 Contrast
Adjust contrast of local display (-10...+10).
C5.3 1. Meas. Page
Configuration of the first measurement display page.
C5.3.1 Function
Select: One Value / Two Values / Three Values / One Value & Bargraph / Two Values &
Bargraph
Function
Setting / Description
C3 Communication