7 Maintenance and fault rectification
OPTISOUND 3020 C • Two-wire 4 … 20 mA/HART
30507-EN-190318
Error
Cause
Rectification
E013
no measured value available Sensor in boot phase
Sensor does not find an echo, e.g. due to faulty installation
or wrong parameter adjustment
E017
Adjustment span too small
Carry out a fresh adjustment and increase the distance be-
tween min. and max. adjustment
E036
no operable sensor software Carry out a software update or send instrument for repair
E041
Hardware error, electronics
defective
Exchange the instrument or send it in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Set up
" may have to be carried out again.
7.3 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with ap-
propriate Ex approval may be used.
If there is no electronics module available on site, one can be ordered
from the Krohne agency serving you.
7.4 How to proceed if a repair is necessary
If it is necessary to repair the instrument, please contact the responsi-
ble Krohne agency.