34
6 Set up with the display and adjustment module
OPTISOUND 3020 C • Two-wire 4 … 20 mA/HART
30507-EN-190318
The values in bold font represent the data of the factory setting.
In HART multidrop mode, the current is constantly 4 mA. This value
does not change even in case of failure.
Current output
Characteristic: 4-20 mA
▼
Failure mode: 22 mA
▼
Min. current 3.8 mA
▼
In this menu item you simulate a user-defined level or pressure value
via the current output. This allows you to test the signal path, e.g.
through connected indicating instruments or the input card of the
control system.
The following simulation variables are available:
•
Percent
•
Current
•
Pressure (with pressure transmitters)
•
Distance (with radar and guided radar (GWR))
With Profibus PA sensors, the selection of the simulated value is
made via the "Channel" in the menu "
Basic adjustments
".
How to start the simulation:
1. Push
[OK]
2. Select the requested simulation variable with
[->]
and confirm
with
[OK]
.
3. Set the requested numerical value with
[+]
and
[->]
.
4. Push
[OK]
The simulation is now running, with 4 … 20 mA/HART a current is
output and with Profibus PA or Foundation Fieldbus a digital value.
How to interrupt the simulation:
→
Push
[ESC]
Information:
The simulation is automatically terminated 10 minutes after the last
pressing of a key.
Simulation
Start simulation?
If the function "
Reset
" is carried out, the sensor resets the values of
the following menu items to the reset values (see table):
4)
Function
Reset value
Sensor address
126
Max. adjustment
0 m(d)
Service - Simulation
Service - Reset
4)
Sensor-specific basic adjustment.