INSTALLATION
2
11
OPTIFLUX 4000
www.krohne.com
10/2021 - 4003872405 - QS OPTIFLUX 4000 R08 en
2.8.4 T-section
2.8.5 Open discharge
2.8.6 Pump
Figure 2-10: Distance behind a T-section
1
t
10 DN
Figure 2-11: Installation in front of an open discharge
Figure 2-12: Installation behind a pump
INFORMATION!
Recommended position to install a flowmeter is downstream a pump (on a position where the
flow disturbances of the pump are resolved).
An electromagnetic flowmeter can be installed in the suction line of a pump if there is no
cavitation in the pipeline system.