INSTALLATION
2
13
OPTIFLUX 4000
www.krohne.com
10/2021 - 4003872405 - QS OPTIFLUX 4000 R08 en
2.8.9 Flange deviation
2.8.10 Mounting position
•
Install the flow sensor with the signal converter aligned upwards or downwards.
•
Install the flow sensor in line with the pipe axis.
•
Pipe flange faces must be parallel to each other.
CAUTION!
Max. permissible deviation of pipe flange faces:
L
max
- L
min
d
0.5 mm / 0.02"
Figure 2-16: Flange deviation
1
L
max
2
L
min
Figure 2-17: Mounting position