6
OPERATION
82
OPTIFLEX 8200 C/F/S
www.krohne.com
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
Switch Function
The switch function for output 2. Make
a selection from a list of switch
functions to set the switch signal to the
function that the device must monitor.
For more data about the switch
function, refer to
Relay output
on page
100.
This function is available if Optional
Optional
Optional
Optional
Output Mode
Output Mode
Output Mode
Output Mode is set to "RELAY".
LEVEL, LEVEL CONVERSION,
DISTANCE, DISTANCE CONV.,
INTERFACE LEVEL,
INTERFACE CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST. CONV.,
LAYER, LAYER CONVERSION,
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER TEMPERATURE,
SENSOR TEMPERATURE,
CURRENT mA, CURRENT %,
ERROR LIST
1
Set
Point/Threshold
This function gives the point or
threshold (level, distance etc.) when
the device will send the relay signal.
This function is available if Optional
Optional
Optional
Optional
Output Mode
Output Mode
Output Mode
Output Mode is set to "RELAY" and
Switch Function
Switch Function
Switch Function
Switch Function is not set to "ERROR
LIST".
min-max:
2
—
Alarm Mode
"LOW LEVEL ALARM" tells the device
to send the relay signal when the
quantity of product in the tank is less
than the threshold. "HIGH LEVEL
ALARM" tells the device to send the
relay signal when the quantity of
product in the tank is more than the
threshold.
This function is available if Optional
Optional
Optional
Optional
Output Mode
Output Mode
Output Mode
Output Mode is set to "RELAY" and
Switch Function
Switch Function
Switch Function
Switch Function is not set to "ERROR
LIST".
LOW LEVEL ALARM,
HIGH LEVEL ALARM
—
Hysteresis
If Alarm Mode
Alarm Mode
Alarm Mode
Alarm Mode is set to "LOW LEVEL
ALARM", this gives the quantity of
product above the threshold where the
relay goes back to "off".
If Alarm Mode
Alarm Mode
Alarm Mode
Alarm Mode is set to "HIGH LEVEL
ALARM", this gives the quantity of
product below the threshold where the
relay goes back to "off".
This function is available if Optional
Optional
Optional
Optional
Output Mode
Output Mode
Output Mode
Output Mode is set to "RELAY" and
Switch Function
Switch Function
Switch Function
Switch Function is not set to "ERROR
LIST".
min-max:
2
—
Error List
If Switch Function
Switch Function
Switch Function
Switch Function is set to "ERROR
LIST", Error List
Error List
Error List
Error List replaces the
Point/Threshold, Alarm Mode and
Hysteresis steps in this procedure.
This tells the device to send a relay
signal if the error condition specified in
this step occurs.
OVERFILL, TANK EMPTY,
INTERFACE LOST,
CONV. TEMP. < MINI,
CONV. TEMP. > MAXI,
SNSR. TEMP. < MINI,
SNSR. TEMP. > MAXI,
DIELCT. CALC. FROZ.,
LEVEL LOST
—
Process
analysis...
Probe analysis...
Menu
No.
Function
Function description
Selection list or range of
values
Default