6
OPERATION
88
OPTIFLEX 8200 C/F/S
www.krohne.com
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
1.4.0 Application Setup
1.4.0 Application Setup
1.4.0 Application Setup
1.4.0 Application Setup
Use this quick set-up procedure to give the settings about the application type and the dielectric constant of
the top product.
Application Type
This function tells the device what to look
for in the tank and what to do with the
measurement signals.
If the device has the Dynamic Gas-phase
Dynamic Gas-phase
Dynamic Gas-phase
Dynamic Gas-phase
Compensation
Compensation
Compensation
Compensation (DGC) option, the device will
do a process analysis to measure the
dielectric constant of the gas above the
product in the tank.
LEVEL, LEVEL +
INTERFACE MIXED,
LEVEL + INTERFACE
UNMIXED, INTERFACE
(FULLY SUBMERGED
PROBE), LEVEL WITH
GAS PHASE
COMPENSATION
5
LEVEL
Epsilon R
Product
This is the dielectric constant of the top
product.
Known, Unknown
If Epsilon R Product
Epsilon R Product
Epsilon R Product
Epsilon R Product is "Known", give the
correct value for the dielectric constant.
min-max: 1....115
67.5
If Epsilon R Product
Epsilon R Product
Epsilon R Product
Epsilon R Product is "Unknown".
What is the product family?
ACIDS, ALCOHOL, BASE,
HYDROCARBON,
LIQUID GAS,
MINERAL OIL, SOLVENT,
WATER-BASED, OTHER
OTHER
1.5.0 Options
1.5.0 Options
1.5.0 Options
1.5.0 Options
Options can be included in the customer order or you can buy this option after delivery. For more data, speak
or write to your supplier.
1.5.1
Interface Capab.
A device option. This function shows if the
Interface Capability
Interface Capability
Interface Capability
Interface Capability mode is set to on (the
menu item shows the message "option is
active").
You can set the Interface Capability
Interface Capability
Interface Capability
Interface Capability mode
to on if you enter a code in this menu item.
If you do not have this code, contact your
supplier to buy this option.
1.5.2
Gas Phase Comp. A device option. This function shows if the
Dynamic Gas-phase compensation
Dynamic Gas-phase compensation
Dynamic Gas-phase compensation
Dynamic Gas-phase compensation (DGC)
mode is set to on (the menu item shows
the message "option is active").
You can set the DGC mode to on if you
enter a code in this menu item. If you do
not have this code, contact your supplier to
buy this option.
1.6.0 Maintenance Setup
1.6.0 Maintenance Setup
1.6.0 Maintenance Setup
1.6.0 Maintenance Setup
1.6.1
Converter Type
Converter
Version
The signal converter is available in 3
versions. Make a selection from the list. If
you set Converter Type
Converter Type
Converter Type
Converter Type to "S: REMOTE
SENSOR", then you must also enter the
remote cable length.
C: COMPACT,
F: REMOTE CONVERTER
S: REMOTE SENSOR,
3
Remote Cable
Length
The length of the sensor extension. If the
device is the sensor extension with
compact version (S), this is the coaxial
cable between the converter and the
process connection.
0...15 m
3
Menu
No.
Function
Function description
Selection list or range
of values
Default