6
OPERATION
90
OPTIFLEX 8200 C/F/S
www.krohne.com
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
Menu
No.
Function
Function description
Selection list or range
of values
Default
2.0.0 Supervisor
2.1.0 Identification
2.1.0 Identification
2.1.0 Identification
2.1.0 Identification
2.1.1
Serial Number
The device serial number.
Read only.
2.1.2
Conv Firm
Version
The converter firmware version.
Read only.
2.1.3
Sens Firm
Version
The sensor firmware version.
Read only.
2.1.4
HMI Firm Version The HMI (device display screen) firmware
version.
Read only.
2.1.5
Electronic
Revision
Electronic Revision
Electronic Revision
Electronic Revision
Electronic Revision is a series of numbers
used to record the revision status of
embedded software (firmware) in
electronic equipment assemblies. It gives
data on the type of changes made and the
effect that changes have on compatibility.
Read only.
2.1.6
Mechanical
Traceability
The serial number for the probe and
process connection.
Read only.
2.2.0 Tests
2.2.0 Tests
2.2.0 Tests
2.2.0 Tests
2.2.1
Set Curr.Output
I1
Set Current Output. This sets analogue
output 1 to a test value [mA] selected from
a list. Output will change to the selected
value, independent of the measured value.
3.5, 4, 6, 8, 10, 12, 14, 16,
18, 20 or 22 mA
3.5 mA
2.2.2
Diagnostic
This starts the hardware test. Push [
]
and [
] many times to show: the
functioning time, converter temperature,
current on loop, load current , voltage
5.3 V, voltage on capacitors, voltage 3.3 V,
reference pulse amplitude, flange pulse
amplitude, level pulse amplitude, probe
end pulse amplitude, reset counter and
device status (this includes warning and
error messages that are "on" at this time).
Read only.
2.2.3
Set Current
Output I2
Set Current Output. This sets analogue
output 2 to a test value [mA] selected from
a list. Output will change to the selected
value, independent of the measured value.
3.5, 4, 6, 8, 10, 12, 14, 16,
18, 20 or 22 mA
3.5 mA
2.2.4
Switch Output
test
This function sends a test signal to show
that the relay is open or closed.
OPEN, CLOSE
OPEN
2.2.5
Proof Test
Not yet available. If the device has the SIL
option, it is necessary to do proof tests to
make sure that the safety function is
applicable to the full measuring range. We
recommend that you do a proof test
immediately after you install and start the
device.
2.3.0 Basic Parameters
2.3.0 Basic Parameters
2.3.0 Basic Parameters
2.3.0 Basic Parameters
2.3.1
Tank Height
The distance from the tank connecting
flange face / thread stop down to the tank
bottom.
min-max:
0
…
99.999 m /
0
…
328.08 ft
If tank height is
not specified in
customer order,
the probe
length value is
used