ELECTRICAL CONNECTIONS
48
OPTIFLEX X200
www.krohne.com
09/2018 - 4006564001 - AD IECEX OPTIFLEX x200 R01 en
•
The electrical wiring must agree with the applicable standards (e.g. IEC 60079-14).
•
Do not remove more than 6 mm / 0.2
¨
of insulation from the electrical wire.
•
Put the electrical wires in position and safely attach them to prevent damage. The electrical
wires must also be a sufficient distance from hot surfaces.
•
If it is necessary, make sure that the electrical wire insulation gives good protection from
corrosion.
•
Make sure that the device is connected to a PELV (protective extra-low voltage) circuit.
•
Make sure that electrical wires for the converter are isolated from the ground of the
hazardous area. This data is also applicable to the equipotential bonding conductors (PE).
•
Make sure that unused electrical wires and shields are safely connected to the ground
potential of the hazardous area. If this is not possible, make sure that each of the unused
electrical wires are safely isolated (other electrical wires, ground etc.) and rated for a test
voltage
≥
1500 V
RMS
.
Load resistor (4...20 mA - HART output option)
If the device uses the HART
®
communication protocol to send data, connect the load resistor to
the positive terminal of the power supply in a non-hazardous location and ground the negative
connection.
If it is necessary to connect the load resistor to the negative terminal, the loop resistance must
not be more than 350 ohms.
Remote (Field) version
Remote (Field) version
Remote (Field) version
Remote (Field) version
The signal cable (between the converter electronics and the probe electronics) is supplied by the
manufacturer for IECEx applications. The signal cable cannot be changed by the user. For more
data, speak to the supplier.
3.7.3 Supply voltage
Level transmitter with the 4...20 mA / switch output options
CAUTION!
Do not ground the positive connection.
Terminals
Minimum voltage at
output terminals
Maximum voltage at
output terminals
[V DC]
I/O 1
13.5
34
I/O 2
11.5
34
Switch (AC 1)
5 (V AC)
48 (V AC)
Switch (DC 1)
2
24
WARNING!
The voltage difference between earth potential and the negative input terminal of the device
must be less than 13 V. A higher voltage can cause a leakage current. Leakage currents can have
an effect on the performance of the device and can cause the operation of fuses in the device. Do
this check before energizing the circuit.