.52+1(
BM 70 A Kurzanleitung
Seite: 4
4. Entwurf 03/97
2.2 Mechanical installation
Hazardous-duty systems
•
The BM 70 A Ex is certified in conformity with European Standard for use in
Zone 0, 1 and 2 hazardous locations (Wave-Stick: Zones 1, 2 to PTB, Zone 0 to
SEV).
•
The BM 70 A Ex is approved for use in dust locations of Zones 10 and 11 (but
not the Wave-Stick).
•
Attention is drawn to the information given on the nameplate and the
specifications in the approval certificates.
Safety
•
Surface temperature: The housing of the signal converter can, in extreme
ambient conditions, assume temperatures of more than 70°C!
•
Check material compatibility of antenna, extension, flange, gaskets, and PTFE
(used in all versions) with the product!
Mounting on the tank nozzle
Devices with horn antenna:
The antenna should project out of the nozzle. If necessary, use an antenna
extension.
Tankstutzen
Tankstutzen
Antennen -
Verlängerung
Wave-Stick
Note the requirements imposed on nozzle diameter and nozzle length: