BM 70 A Kurzanleitung
Seite: 14
4. Entwurf 03/97
Sequence for setting parameters (example)
The following description refers to a storage tank with the parameter examples taken
from the illustration in this Section. If the device no longer contains the default
parameters, the keystroke combination for entering the numerical values may differ.
Activity
Keys to be
actuated
Content of BM 70 A
display after activity
carried out
Entry into configuration menu
Fct. 1.0
OPERATION
Setting the parameter: tank height
Fct. 3.1.1
Tankheight
Display of default value
10.000 m
Input of tank height "5.30 m"
9x
5x
3x
05.300
M
Confirm tank height and move to block
distance
Fct. 3.1.2
Blockdist
Display default value
0.5000 m
Enter block distance "0.60 m"
0.6000 m
Confirm block distance and move to current
output configuration
Fct. 3.3
Sig.output.
Move to lower range value
Fct. 3.3.3
Scale 4 mA
Display default value
+ 00.000 m
Enter lower range value (0.4 m = 4 mA)
3x
4x
+ 00.400 m
Confirm lower range value and move to full-
scale range value
Fct. 3.3.4
Scale. 20mA
Display of default value
010.00 m
Enter full-scale value (4.0 m = 20 mA)
2x
9x
4x
004.00 m
Confirm full-scale value and move to empty
tank spectrum
Fct. 3.5.2
EMPTY.SPECT.
Select: re-record empty spectrum
RECORD
Store changed parameters
Accept. Yes
Confirm and select: averaging
Averaging
Confirm and start recording; then wait for
approx. 2 minutes!
READY
Confirm and move to tank type
7x
Fct. 3.5.9
Tank type
Display of default value
PROCESS-TK.
Select tank type "storage tank"
Storage tank
Return to measurement function with
confirmation of changed parameters
5x
Param.Check
,
then
START
,
then meas.val. display