INSTALLATION
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
#CSK-29-MV R.6 January 2019
6.7 Outdoor Covered Fireplace Installation
An outdoor covered fireplace installation allows a fireplace to be
installed in an outdoor covered area, where the appliance is protected
from direct precipitation.
Follow the instructions and illustration below for installation
procedures. Drawings are for reference only and your fireplace may
look different than shown.
6.7.1 Safety Screen Barriers
Hussong Mfg. highly recommends to use black painted safety barriers
in outdoor installations. Other screen barriers that incorporate
a plated or patina finish are highly susceptible to oxidation and
discoloration.
6.7.2 Requirements
•
Fireplace operation is approved from 40°F to 110°F.
•
All wiring connections shall be in accordance with outdoor
requirements of NECA NFPA 70.
•
All clearances and requirements in this manual must be adhered
to.
FRONT OF
FIREPLACE
A
B
C
C
The width of the overhang to each side of the
appliance (C) must be a minimum of 1/2 or
greater of the roofline elevation (B) above the
base of the fireplace.
The overhang (A) must be a minimum of 1/2 or
greater of the roofline elevation (B) above the base
of the fireplace.
EXAMPLE: If roofline (B) is 10 ft above the base of fireplace, the overhang (A) must be 5 ft
or greater. The width of the overhang to EACH side of the fireplace (C) must be 5 ft or greater.
Figure 6.7, Outdoor Covered Fireplace Installation