Appliance Certification–Requirements for Massachusetts

SECTION 1

 INTRODUCTION

#CAR-39

R.11  February 2022

#CAR-39

R.11  February 2022

7

HUSSONG MFG. CO., INC.

KOZY HEAT FIREPLACES

1.1  Appliance Certification

Laboratory: PFS in Cottage Grove, Wisconsin 
Standards: 
ANSI Z21.88-2017/CSA 2.33-2017, Vented Gas Fireplace Heaters
CSA 2.17 2017, Gas-Fired Appliances for Use at High Altitudes
This installation must conform with local codes, or in the absence of 

local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or 

the Natural Gas and Propane Installation Code, CSA B149.1.

1.2  California Proposition 65 Warning

WARNING:

 This product can expose you to chemicals including 

Carbon Monoxide, that is an externally vented by-product of fuel 

combustion, which is [are] known to the State of California to cause 

birth defects or other reproductive harm. For more information, visit 

www.P65Warnings.ca.gov.

1.3  Requirements for  the 

Commonwealth of Massachusetts

The following requirements reference various Massachusetts and 

national codes not contained in this manual.

For all sidewall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part for 

residential purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust vent termination 

is less than (7) feet above finished grade in the area of the venting, 

including but not limited to decks and porches, the following 

requirements shall be satisfied:

1.3.1  Installation of Carbon Monoxide Detectors

At time of installation of side wall horizontally vented gas fueled 

equipment, the installing plumber or gas-fitter shall observe that 

a hard wired carbon monoxide detector with an alarm and battery 

back-up is installed on the floor level where the gas equipment is 

to be installed. In addition, the installing plumber or gas-fitter shall 

observe that a battery operated or hard wired carbon monoxide 

detector is installed on each additional level of the dwelling, building 

or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner 

to secure the services of qualified licensed professionals for the 

installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or attic, the hard wired carbon 

monoxide detector with alarm and battery back-up may be installed 

on the next adjacent floor level. In the event that the requirements 

of this subdivision can not be met at the time of completion of 

installation, the owner shall have a period of thirty (30) days to 

comply with the above requirements; provided, however, that during 

said thirty (30) day period, a battery operated carbon monoxide 

detector with an alarm shall be installed.

1.3.2  Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the 

above provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

1.3.3  Signage

A metal or plastic identification plate shall be permanently mounted 

to the exterior of the building at a minimum of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the 

horizontally vented gas fueled heating appliance or equipment. The 

sign shall read, in print no less the one-half inch (½) in size, “GAS VENT 

DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”. 

1.3.4  Inspection

The state or local gas inspector of the side wall horizontally vented 

gas fueled equipment shall not approve the installation unless, upon 

inspection, the inspector observes carbon monoxide detectors and 

signage installed in accordance with the provisions of 248 CMR 5.08 

(2) (a) 1 through 4.

1.3.5  Exemptions

The following equipment is exempt from 248 CMR 5.08 (2) (a) 1 

through 4: The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition of NFPA 54 as 

adopted by the Board; and Product Approved side wall horizontally 

vented gas fueled equipment installed in a room or structure separate 

from the dwelling, building or structure used in whole or in part for 

residential purposes.

1.3.6  Manufacturer Requirements

1.3.6.1  Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally 

vented gas equipment provides a venting system design or venting 

system components with the equipment, the instructions provided 

by the manufacturer for installation of the equipment and the 

venting system shall include:
• 

Detailed instructions for the installation of the venting system 

design or the venting system components; and

• 

A complete parts list for the venting system design or 

venting system.

1.3.7  Gas Equipment Venting 

System NOT Provided

When the manufacturer of Product Approved side wall horizontally 

vented gas equipment does not provide the parts for venting the 

flue gases, but identifies “special venting systems”, the following 

requirements shall be satisfied by the manufacturer:
• 

The referenced “special venting systems” instructions shall 

be included with the appliance or equipment installation 

instructions and;

• 

The “special venting systems” shall be Product Approved by the 

Board, and the instructions for that system shall include a parts 

list and detailed installation instructions.

A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all venting 

design instructions shall remain with the appliance or equipment at 

the completion of the installation.

1.0  INTRODUCTION

Содержание CAR-39

Страница 1: ...et permanently located manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is...

Страница 2: ......

Страница 3: ...fety We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong President Dudley Hussong Board Chairman Homeowner R...

Страница 4: ......

Страница 5: ...tural Draft Vent Termination Clearances 33 7 0 VENTING 34 7 1 Approved Vent Systems 34 7 3 Natural Draft Vent Restriction 35 7 4 Vent Heat Shield Assembly Installation 36 7 5 Natural Draft Vent Instal...

Страница 6: ......

Страница 7: ...ring said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 1 3 2 Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accord...

Страница 8: ...SA B149 1 Natural Gas and Propane Installation Code local authorities or codes having jurisdiction in you area regarding derate guidelines 2 1 1 1 US Installations Refer to the American Gas Associatio...

Страница 9: ...PLACES 2 3 Appliance Dimensions 87 16 214mm 1915 16 507mm 22 559mm 34 876mm 2 51mm 139 16 345mm 25 16 58mm 35 908mm 38 984mm 297 16 747mm 10 254mm 35 16 85mm 815 16 226mm LEFT SIDE FRONT SIDE RIGHT SI...

Страница 10: ...the drawing below for overlap dimensions to ensure the barrier can fit with finishing materials For installation instructions refer to section 4 3 SAFETY BARRIER INSTALLATION on page 28 34 882mm 5 8...

Страница 11: ...EXTERIOR AND INTERIOR HEAT TRANSFER KIT COVER PLATE S on page 21 If planning to convert to propane it is easier to complete the gas conversion before framing in the fireplace See the LCK C39 D manual...

Страница 12: ...shields and insulation piece are adjustable to accommodate the installation of non combustible material If you install the stand off assembly in a forward position the non combustible material will o...

Страница 13: ...3 Place the insulation piece in between the two stand off assemblies as shown The insulation piece must be pushed tight against the required non combustible material board 4 Attach the lower header h...

Страница 14: ...acing away from the fireplace 3 Secure the nailing flanges to the fireplace with screws provided through the slots in nailing flanges 4 Bend perforation on nailing flange until parallel with fireplace...

Страница 15: ...front 36 914mm Appliance side to adjacent sidewall 1 1 4 32mm Appliance top to 3 4 19mm trim 10 254mm Mantel 10 254mm deep from appliance top 14 356mm Appliance top to fireplace enclosure top 30 762mm...

Страница 16: ...the appliance This fireplace may be elevated off the floor provided it is properly supported by framing materials and maintains ceiling clearances If installed above floor level a solid continuous pl...

Страница 17: ...maintained A minimum of 1 25mm clearance on the sides and bottom surfaces on the horizontal pipe must be maintained 3 6 2 2 Vertical Terminations Follow vent pipe manufacturer s installation instruct...

Страница 18: ...tion instructions for natural draft vent installation Rigid pipe dimensions in FIGURE 3 6 reflect Simpson Duravent 5 x 8 coaxial pipe Other manufacturers product dimensions may vary Flexible pipe fram...

Страница 19: ...nsulated building envelope and weatherproof membrane are not to be interrupted by fireplace installation See FIGURE 3 8 on the following page Fireplace operation is approved from 40 F to 110 F All wir...

Страница 20: ...ted by fireplace installation Free standing structure weatherproof enclosure INSIDE OUTSIDE INSIDE Minimum weatherproof overhang in front and sides M i n i m u m w e a t h e r p r o o f o v e r h a n...

Страница 21: ...arerequiredspecifically for your application or installation FIGURE 3 9 shows removal of the Heat Transfer Kit cover plates There are 2 square cover plates located on the left and the right side of th...

Страница 22: ...the possibilityofthesheetrocktocrack HussongMfg Co Inc recommends the following methods The front face of the unit to the insulation piece and stand off assembly will accommodate typical 1 2 12mm non...

Страница 23: ...IREPLACES 64 1638mm 34 876mm 19mm trim 14 356mm 16 406mm 18 457mm 10 254mm 14 356mm 12 305mm 10 254mm Non combustible material only Insulation piece MUST rest against non combustible material Combusti...

Страница 24: ...EPLACES 64 1638mm 34 876mm 6 152mm 12 305mm 12 305mm 9 229mm 6 152mm Non combustible Zone Non combustible material only Insulation piece MUST rest against non combustible material Combustible floor No...

Страница 25: ...FacingandFinishingRequirements SECTION 4 FACING AND FINISHING CAR 39 R 11 February 2022 25 HUSSONG MFG CO INC KOZY HEAT FIREPLACES 64 1638mm 1 32mm unlimited Figure 4 3 Sidewall Clearance...

Страница 26: ...HUSSONG MFG CO INC KOZY HEAT FIREPLACES 10 254mm 39 1010mm Non combustible Zone NOTE A 41 1 4 x 10 1 2 non combustible material board is supplied with the fireplace and allows a 3 4 overlap onto frami...

Страница 27: ...shown below Insert the tabs on the trim panel into the slots on the bottom opening of the fireplace 3 If installed remove the stand off assembly header heat shields and insulation piece 4 Install the...

Страница 28: ...corresponding holes in the inside flange on each side of the firebox floor The bottom frame piece is shipped with safety barrier C39 RSF2 and must be installed 3 Center the screen front over the glass...

Страница 29: ...tment as you see fit NOTE The position of the louver should match with the desired position of the notched tabs needed for your installation The louver in the first notch position will match with the...

Страница 30: ...ur installation The louver in the first notch position will match with the first notch position in the notched tabs the louver in the second notch position will match the second notch in the notched t...

Страница 31: ...pply piping system by closing its individual manual shut off valve A listed and Commonwealth of Massachusetts approved 1 2 13mm tee handle manual shut off valve and flexible gas connector are to be co...

Страница 32: ...Feet Meters Flat to 6 12 1 0 0 30 Over 6 12 to 7 12 1 25 0 38 Over 7 12 to 8 12 1 5 0 46 Over 8 12 to 9 12 2 0 0 61 Over 9 12 to 10 12 2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 0 1...

Страница 33: ...12 30cm 9 23cm K Clearance to mechanical air supply inlet 6 1 83m 3 91cm above if within 10 3m horizontally Massachusetts 10 3m L Clearance above paved sidewalk or paved driveway located on public pr...

Страница 34: ...manual for complete installation instructions Vent installation must conform with venting requirements and restrictions as outlined in this manual 7 2 Venting Requirements NOTE Consult the local and...

Страница 35: ...will create the least amount of restriction Closing the baffle restrictor will create more vent exhaust restriction Follow FIGURE 7 1 for restrictor plate installation before attaching venting or thro...

Страница 36: ...nding screw holes located in front of the flue outlet on the top of the fireplace 3 Secure the vertical vent heat shield to the fireplace with 2 attachment screws provided in the components package 7...

Страница 37: ...7 5 1 Vertical Terminations Natural Gas and Propane i Minimum Maximum Vertical Terminations 4 1219mm minimum vertical length 50 15 24m maximum vertical length termination cap Hussong Mfg Co Inc recomm...

Страница 38: ...st be installed when installing minimum vertical rise combination venting Refer to section 7 4 on page 36 i Minimum 6 Vertical Venting Minimum Maximum Horizontal Termination 6 152mm minimum vertical r...

Страница 39: ...ons must be within the shaded area in FIGURE 7 4 25 7 6m maximum vertical rise 25 7 6m maximum horizontal run 50 15 2m of total length Maximum of 5 90 elbows For each additional 90 elbow used after th...

Страница 40: ...be installed when installing minimum vertical rise combination venting Refer to Section 7 4 on page 36 i Minimum 12 Vertical Venting Minimum Maximum Horizontal Termination 12 305mm minimum vertical ri...

Страница 41: ...s must be within the shaded area in FIGURE 7 5 25 7 6m maximum vertical rise 25 7 6m maximum horizontal run 50 15 2m of total length Maximum of 5 90 elbows For each additional 90 elbow used after the...

Страница 42: ...h overlapping the heat shields as necessary to accommodate wall thickness The sections must overlap a minimum of 1 1 2 38mm Secure to exterior wall with 4 screws not provided 4 Follow vent manufacture...

Страница 43: ...ectrical power from the fireplace before performing this task ATTENTION If converting to propane complete the conversion before installing any light kit components Follow instructions provided with th...

Страница 44: ...ons and illustrations for proper log placement 1 Position the ember panel in front of the burner 2 Align the slots in the bottom of log C39 1B with the mounting pins on the back log plate burner brack...

Страница 45: ...the light kit assembly 11 Remove and save 10 screws securing the control board Raise the control board to unplug control module and fan wiring from the control module 12 Lift the control board and co...

Страница 46: ...when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 9...

Страница 47: ...n all electric power to the appliance 10 Press the wireless remote POWER button 11 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technici...

Страница 48: ...g the UP and DOWN arrows highlight the PILOT icon and press SELECT 3 Use the UP and DOWN arrows to turn the pilot on demand ON or OFF then press SELECT A single beep will be emitted from the control m...

Страница 49: ...into a standby mode if no buttons are pressed within 5 minutes Press the POWER button to reactivate the remote control to ON mode Active functions will be displayed once in ON mode POWER BUTTON MENU...

Страница 50: ...Appliance With the system in the ON position press the remote control POWER button to turn OFF the appliance Functions AUX1 AUX2 and Pilot on Demand can be accessed when the remote control is OFF Onl...

Страница 51: ...s function 1 Press the MENU button to activate the menu 2 Using the UP and DOWN arrows highlight the THERMO icon and press SELECT 3 Use the UP and DOWN arrows to turn the THERMO ON or OFF then press S...

Страница 52: ...the UP and DOWN arrows highlight the AUX1 icon and press SELECT 3 Use the UP and DOWN arrows to adjust to desired light kit intensity The transmission indicator icon will flash and a single beep will...

Страница 53: ...etween the minimum and maximum recommended pressure settings 4 Turn off burner and pilot 5 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not...

Страница 54: ...t at slight increments until desired look is achieved The air shutter on this appliance is factory set for horizontal terminations and may need adjustment for natural gas installations depending on ve...

Страница 55: ...e desired flame appearance 3 Tighten screws after adjustment 4 Reinstall the glass frame assembly and safety barrier 11 2 2 2 Restrictor Plate Installation 1 Remove the safety barrier and the glass fr...

Страница 56: ...c in this manual to determine that all wiring connections are secure and correct Control module selector switch not set properly Verify the ON OFF REMOTE selector switch is ON mode or REMOTE mode Gas...

Страница 57: ...at operation is turned OFF Pilot and burner extinguish while in operation No propane in tank Check propane tank Refill if necessary Incorrect glass assembly installation Refer to section 8 1 GLASS FRA...

Страница 58: ...vent system Check the vent pipes for leaks and the vent cap for debris Repair the vent pipes or remove debris from vent cap if necessary No reaction to command Battery back batteries or remote contro...

Страница 59: ...to section 7 0 VENTING on page 34 Performed by Qualified Service Person Frequency Annually Action Examination of the vent system is required Inspect the condition of vent and vent terminal for sooting...

Страница 60: ...of the flame safety system Pilot or Flame rectification device Visually check pilot light when in operation Inspect and ensure the lighting of the main burner occurs within 4 seconds of the main gas v...

Страница 61: ...xen Conversion Kit Natural Gas DEX 191 1 Propane Dexen PSE IPI Pilot Assembly 700 191 1 LCK C39 D Dexen Conversion Kit Propane DEX RC3 Dexen Transmitter Remote Control C39 035A Burner Tube 700 094 P P...

Страница 62: ......

Страница 63: ...s warranty does not cover installation and operational related problems such as environmental conditions nearby trees buildings hilltops mountains inadequate venting or ventilation excessive offsets n...

Страница 64: ......

Отзывы: