3.8.2.1 Top Vented Cavity
Alternative Installations
•
Figure 3.21 shows an alternative installation for the top vented
cavity option with an air discharge overhang in front of the air
discharge opening. This installation method can provide a means
to visually hide the air discharge opening.
FRONT VIEW
SIDE VIEW
TOP VIEW
Enclosure top
must be installed
1
½
”
(38mm) Min
Max
6”
(152mm)
8”
(203mm) Min
Air Discharge Overhang
Air discharge
opening entire top
at 1½” (38mm) MIN
Air discharge opening
Air discharge overhang
Air discharge overhang
Width of fireplace chamber
8”
(203mm) Min
6”
(152mm) Max
76”
(1930mm)
Min
Figure 3.21, Top Vented Cavity Alternative Installation with Overhang
TOP VENTED CAVITY INSTALLATIONS
30
FRAMING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
#CLW-50 R.6 November 2021