3.8.1.1 Single Opening Vented Cavity Option
Alternative Installations
•
Figure 3.16 shows an alternative installation for the single
opening vented cavity installation with an air discharge
overhang in front of the air discharge opening. This installation
method can provide a means to visually hide the air discharge
opening.
Air Discharge Overhang
AIR DISCHARGE OPENING
Enclosure top
must be installed
Air discharge overhang
Air Discharge
Opening Front
(3” x 43”) MIN
43” (1092mm)
MIN
51” (1295mm)
MIN
4” (101mm) MIN
6” (152mm) MAX
6” (152mm) MAX
8” (203mm) MIN
74”
(1880mm)
MIN
3” (76mm)
MIN
SIDE VIEW
FRONT VIEW
TOP VIEW
Figure 3.16, Single Opening Vented Cavity with Overhang
SINGLE OPENING VENTED CAVITY INSTALLATION
#CLW-40 R.3 November 2021
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FRAMING
25