8.3 System Separator for Fresh Water:
Servicing
The regular servicing of the System Separator BA is obligatory.
Accordingly, service contracts between the operating company and the installer make sense. The checking of the correct and
proper functioning of the valves takes place after the first year of operation, then at intervals dependent on the operating
conditions, but after one year at the latest. The ball valve connections present in each pressure zone enable a functional
check using an appropriate pressure measurement device (Service Case No. 6600.00.902). The design of the system
separator with a cartridge system allows simple and problem-free servicing of the valves.
Fault
Cause
Remedy
Discharge valve opens without discernible
cause
Water hammer in the water network
Fit a pressure release device before the
system separator
Fluctuating inlet pressure
Fit a pressure reducer before the system
separator
Cartridge insert is dirty
Remove and clean the cartridge insert
Discharge valve doesn't close
Sediment on the valve seat
Remove and clean or replace the cartridge
insert
Damaged O-ring
Remove and replace the cartridge insert
Leaking discharge valve
Remove and clean or replace the cartridge
insert
Flow rate too low
Input-side dirt trap is blocked
Remove and clean the dirt trap
No.
Description
Nominal
Size
1
Cartridge insert complete
3/8
”
2
Backflow preventer complete
3/8
”
3
Drain connection
Function Description:
System separators of the type BA are divided in 3 pressure zones. In Zone (1)
the pressure is higher than that in Zone (2) and there higher than that in Zone
(3). A discharge valve is connected to Zone (2) which opens at the latest when
the differential pressure between Zone (1) and (2) has fallen to 0.14 bar. Water
from Zone (2) flows into the open, both non-return valves close and thereby
separate Zone (2) from Zones (1) and (3). Thus, the risk of back pressure or
back suction into the supply network is avoided. The pipeline is disconnected
and the drinking water network is protected
2
1
3