AIR-SEP
Pressure Maintenance with AIR-SEP
SmartControl
16
KOREX Benelux B.V.
10.
Briefly open (3-5 seconds) the ball valve (10a) to vent the pressure maintenance pump (10). The pressure in the
system falls simultaneously. Close the ball valve again.
The system pressure can be read off from the display (
“
Pressure
… /
current:
”
).
11.
Then tap the
“
Start pump
”
button. The pressure maintenance pump now runs for a max. 60 seconds and the system
pressure increases. It is possible - depending on the pressure situation - that the overflow valve is simultaneously
active.
By tapping on
“
Stop pump
”
the pump operation is stopped.
Advice!
In the event of no or only a small pressure increase, repeat Points 10 and 11 until
the
“
Pressure current
”
is the same as the
“
Pressure set
”
.
12.
The pressure maintenance pump is now ready for operation.
13.
By tapping the buttons + you return to the homepage.
14.
Now switch on the AIR-SEP
unit. To do so, press the switch below the display.
The green LED on the switch indicates the operational readiness. The display indicator of the control changes to
"ON" The AIR-SEP
now works in Standard Mode: Pressure maintenance with interval degassing.
15.
If the system pressure is within the desired pressure maintenance, after approx. 1 minute the first degassing interval
begins
Indicator water magnetic valve (OFF / ON)
Indicator pressure maintenance pump (OFF / ON)
Indicator current pressure (system pressure)
Indicator control (OFF / ON)
Indicator set pressure / switch-on point
Indicator Lower Level (OFF / ON)
10
10a
11
11a
9
10
10a
9