AIR-SEP
Pressure Maintenance with AIR-SEP
SmartControl
www.korexbenelux.com
15
5.2
Commissioning
1.
Open the technical level. First remove the magnetic frame from the display. Then remove the 4 knurled screws from
the front cover (or only the one at the front and loosen the 2 at the sides), gently pull the cover away from the front
and lift it off.
2.
Open the shut-off (1a) of the resupply connection.
Advice!
When using AIR-SEP
softening or demineralization cartridges, also use this user manual and follow the
instructions!
3.
Open the system connections: Ball valve and ball valve with safety cap (3a + 3b and 2b + 2c).
4.
Switch on the main fuse on the electrical cabinet.
Advice!
The switch on the AIR-SEP
must be switched off (up position)!
5.
The AIR-SEP controller starts. Wait until the LED lights up constant green.
6.
Tap
–
using the stylus or finger
–
the flag with the language of your choice. You are taken to the homepage.
7.
Tap the top right-hand button . You are taken to the
“
Automatic Mode
”
page. Then tap the centre gear wheel button
to open the
“
Settings
”
page. Enter the
Password
“
Asdf
”
and confirm your entry by tapping the green tick.
8.
As the AIR-SEP
unit has been prefilled, to start with there is sufficient water in the vessel
(
Lower Level
=
“
NU
”
=
“
OFF
”
).
If the
“
NU
”
=
“
ON
”
the unit has not been filled enough (see 5.1 Section 6)!
Advice!
The pressure maintenance pump is blocked with the active "Lower Level" (NU = ON)!
9.
To check the resupply, tap the
“
Start resupply
”
button. The magnetic valve opens for a max. 60 seconds and top-up
water flows into the AIR-SEP
. In doing so, the
“
filling rate
”
must be between 4-7 l/min. The meter reading is
increased by the resupplied volume of water.
The resupply can be stopped early by tapping the
“
Stop resupply
”
button.