VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the
shipping integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing the

system to warm-up. This is particularly important in winter months.

2. Refer to the identification label for proper electrical voltage and current requirements. Then connect

the power cord to a properly grounded and fused electrical supply. Leave the electrical power off.

3. Note the factory thermostat setting which is typically 75 to 80°F.

4. Adjust thermostat to its maximum setting.  

5. If your unit is equipped with an on-off switch, move it to the on position.

6. Turn electrical power on.

7. Verify that the evaporator blower or fan is running.

8. Adjust the thermostat to its minimum setting. The compressor should start. On units equipped with a

short cycle protector, the compressor will have a delayed start of 6 minutes from the time power is
applied to the unit.  

9. Verify that the condenser blower or fan is running. Note, on units equipped with a low ambient kit, the

start of the condenser fan or blower will be delayed until the system pressures rise.

10. Operate the air conditioner for approximately ten minutes. During this period no unusual noise or

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering
air through their respective discharge ports. The cool air should be discharged should be less than
70°F when the room temperature is between 70 and 80°F.  

11. On units equipped with heaters, adjust both the cooling and heating thermostats to their maximum

settings. Verify that the compressor and condenser fan or blower has stopped. Verify elevated
discharge air temperature from the evaporator air discharge.

12. If your unit is equipped with an on-off switch, leave it in the on position.  Return the cooling

thermostat to its original setting.  If unit is equipped with a heater, return the heating thermostat to
its original position.

13. Turn off the electrical power source, and disconnect the air conditioner from the power source.

14. If any cover plug is removed to adjust the unit, make certain to put back in place to maintain the

integrity of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a performance test.

The Air Conditioner must be standing in its proper mounting position for a minimum of

five (5) minutes prior to testing. Failure to follow this procedure will cause permanent

damage to the compressor.

Содержание K2A4C10NP47L

Страница 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 TRIMLINE NP47 SERIES 7 000 10 000 BTU H 900 034 08...

Страница 2: ...ction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Страница 3: ...position All Air Conditioners containing an MM NM P or V as part of the model number are designed to operate in a vertical position only All Air Conditioners containing an H RT or RM in the model num...

Страница 4: ...ements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent dam...

Страница 5: ...nger The warm air inside the enclosure is drawn through the evaporator coil where it is cooled dehumidified and returned Any enclosure moisture accumulated on the evaporator coil is collected in the c...

Страница 6: ...ower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten minutes During this period no unusual noise or vibration should be evident Both the evaporator...

Страница 7: ...B by sliding the studs located on each side panel into the slots on the M TAB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the Air Conditioner side panel and int...

Страница 8: ...ed as high as possible within this area and equal or exceed size of cool air outlets WARM AIR RETURN FROM ENCLOSURE Enclosure opening should be located as high as possible within this area and equal o...

Страница 9: ...K2A4C9NP47L5 9000 125 50 230 50 10 0 150 160 KA3C10NP47R 10000 120 50 115 100 60 50 19 2 18 6 150 160 KA3C10NP47R56 10000 120 50 115 50 60 18 6 19 2 150 160 K2A4C10NP47L 10000 125 50 230 200 60 50 11...

Страница 10: ...ER COND PRESSURE SWITCH OPTIONAL START RELAY S L 2 1 M CAP COMPR 6 8 RELAY 0 1 UL LISTED UNITS ONLY OPTIONAL SWITCH CRANKCASE HEATER HEATER T STAT 55 T STAT 75 BU Y R THERMAL CUTOUT BU R PROTECTOR HEA...

Страница 11: ...off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inle...

Страница 12: ...s valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refr...

Страница 13: ...tat improperly set Low Temperature Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit C...

Страница 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: