6
VI. Pre-Installation Testing
Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.
CAUTION
1
. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to
warm-up. This is particularly important during winter months.
2. Refer to the nameplate for proper electrical voltage and current requirements. Connect the power cord
to a properly grounded and fused electrical supply, leaving electrical power to the unit turned off.
3. Elevate the unit approximately 3" above the floor to ensure proper evaporator airflow. Do not block
evaporator air inlet on bottom of unit.
4. Note the factory thermostat setting which is 75
o
F.
5. Turn the electrical power on.
6. Verify that the evaporator blower or fan is running.
7. Verify that the condenser blower or fan is running.
Note:
The start of the condenser fan or blower will
be delayed until the system pressures rise.
8. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or
vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering
air through their respective discharge ports. The cool air discharged should be less than 70°F when the
room temperature is between 70°F and 80°F.
9. Turn off the electrical power and disconnect the air conditioner from the power source.
10. If any cover plug was removed to adjust the unit, be sure to replace it in order to maintain the integrity
of the closed-loop airflow system.
NOTE:
Before shipment all Kooltronic Air Conditioners are subjected to a performance test.
The temperature of the returning air to the air conditioner is displayed on the exterior
panel of the unit. This is considered the maximum temperature within the enclosure
and not the temperature of the air supplied to the enclosure.
When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75
o
F to 115
o
F
enclosure temperatures, depending on the ambient temperatures.
IMPORTANT NOTE
The air conditioner must be standing in its proper mounting position for a minimum of five
(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to
the compressor. To avoid compressor damage do not tip the unit more than 45° from its
proper mounting position.