background image

VII. Specific Model Data

Mounting

Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging your Air
Conditioner, please read the following information before installation

.

Top-Mounted Air Conditioners for external top installation contain weld-nuts.

Refer to Figure 1 above for the location of all mounting holes and cutouts.

Make sure the cutouts don't interfere with components inside your cabinet

.

Proper alignment of all air inlets and outlets is essential for optimum performance of the Air
Conditioner.

All externally-mounted Air Conditioners must be fully gasketed to ensure proper sealing. This seal is
necessary to maintain the integrity of the closed loop system. See Gasket Placement, Figure 2, above.

Use all existing mounting holes to insure stability and a tight seal.

High strength mounting screws are recommended.

The external drain hose must not be elevated above the exit port. Improper mounting will impede the
flow of condensate and may cause internal malfunctions.

CAUTION

7

When unmounting the unit from the cabinet, make certain

to keep the unit level to avoid spilling any water 

that may be in the condensate pan.

Dimensions, inches [metric], are for reference only and are subject to change.

Dimensions, inches [metric], are for reference only and are subject to change.

FIGURE 1

FIGURE 2

MOUNTING PLAN

GASKET PLACEMENT

13.38

 [340.0]

1.90

 [48.2]

 9.00

 [228.6]

 TYP.

 12.00

 [304.8]

 3.70

 [94.0]

 2.59

 [54.8]

 6.00

 [152.4]

 6.00

 [152.4]

 14.12

 [358.6]

 2.50

 [63.5]

 2.83

 [72.0]

     (6) .312  [7.9]

  DIA. HOLES

 2.06

 [52.3]

 1.19

 [30.2]

  TYP.

   (6) MOUNTING HOLES

 .50

 [12.7]

  

 .50

 [12.7]

  

 .50

 [12.7]

  

 .50

 [12.7]

  

 4.19

 [106.4]

  

 GASKET 1/4" x 1/2"
 KOOLTRO

N

IC P/

N

 0639-55

 START A

N

D E

N

D GASKET 

 MATERIAL HERE. 
 USE O

N

E CO

N

TI

N

UOUS 

 PIECE  OF GASKET. 
 BE

N

D GASKET AROU

N

 THE COR

N

ERS, DO 

N

OT

 STRETCH THE MATERIAL.

 

 APPLY (3) SEPARATE 
 PIECES OF GASKET 
 BET

W

EE

N

 THE 

 PERIMETER GASKET 
 AS SHO

WN

.

 

Содержание Advantage RT Top Mount Series

Страница 1: ...THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 037 03 1 19 CDR 20131 ADVANTAGE...

Страница 2: ...ic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtua...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE...

Страница 5: ...by the compressed refrigerant to the condenser coil Ambient air is then passed through the condenser coil where it absorbs the heat and is then discharged to the environment This unit is equipped wit...

Страница 6: ...no unusual noise or vibration should be evident Both the evaporator and condenser fans or blowers should be delivering air through their respective discharge ports The cool air discharged should be le...

Страница 7: ...trength mounting screws are recommended The external drain hose must not be elevated above the exit port Improper mounting will impede the flow of condensate and may cause internal malfunctions CAUTIO...

Страница 8: ...7 2 13 38 340 0 1 90 48 2 9 00 228 6 TYP 12 00 304 8 3 70 94 0 2 59 54 8 6 00 152 4 6 00 152 4 14 12 358 6 2 50 63 5 2 83 72 0 Drawings and Dimensions KA__C__RTL Dimensions inches metric are for refer...

Страница 9: ...87 0261 287 0261 287 Condenser Blower Capacitor 0452 03 0452 03 0452 03 0452 03 0452 03 Evaporator Blower Motor 0265 03 0194 76 0194 14 0194 76 0194 14 Evaporator Blower Capacitor N A 0452 65 0452 65...

Страница 10: ...ners feature an easily removable inlet filter to facilitate necessary cleaning To access the filter loosen the torx screws and remove the front grille Push the filter upward and pull the bottom edge f...

Страница 11: ...need for replenishment of refrigerant charge When it has been verified by a Certified EPA Technician that a refrigerant shortage does exist the leak must be repaired Then the unit may be evacuated and...

Страница 12: ...essor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: