background image

10

VIII. Maintenance

Kooltronic Air-Cooled Air Conditioners require routine cleaning of the condenser coil (if necessary) and the
air filters to assure unimpeded airflow through the condenser heat exchanger. It is not possible to recommend
specific condenser coil or filter cleaning intervals, since the level and the nature of airborne particulate matter
differs widely with each installation. It is generally sufficient to clean the condenser coil and/or the aluminum
mesh filter when the outer surfaces appear covered with a thin layer of dust, lint or other foreign matter. The
condenser coil can be blown out with air, or washed, depending on the foreign matter involved. Disconnect
power and remove air conditioner from cabinet before using liquids to clean the unit. (see below - 

Filter and

condenser coil service

). The aluminum mesh filter can be washed with warm water. Appropriate

disposable replacement filters are available from Kooltronic.

If routine condenser coil or filter service is neglected or delayed, the air conditioner will not perform at its
design capacity. The first indication of an excessively clogged condenser coil or air filter is usually a gradual
increase of temperature within the equipment cabinet. If operation is continued under these conditions, the
compressor will be shut off by the thermal overload device. The compressor will restart when its external
temperature drops below the protector threshold setting and the compressor will continue to cycle on and off.
Continued operation under these conditions will cause damage, shorten compressor life and void the warranty.

A. Filter and condenser coil service

Kooltronic RT Top Mount Air Conditioners feature an easily removable inlet filter to facilitate
necessary cleaning. To access the filter, loosen the torx screws and remove the front grille. Push the
filter upward and pull the bottom edge forward to remove. After removal, the filters should be flushed
under warm running water with clean side up. If the accumulated dirt is oily, washing in a detergent
bath is recommended, followed by a warm water wash as above. To reinstall the filter, insert the filter
into the filter holder and push the filter back into position. Reinstall the front grille using the torx
screws.

The condenser coil must be cleaned using pressurized air. If liquid cleaning solutions are used, it is
necessary that the air conditioner be removed from the cabinet to avoid liquids draining into the
electronics. Disconnect power before performing this type of operation. 

CAUTION

B. Blowers

The design life of the blowers employed in all Kooltronic Air Conditioners is substantially in excess of
20,000 hours. All Kooltronic condenser and evaporator blowers are equipped with UL/CSA
permanently-lubricated precision ball-bearing motors, with automatic-reset thermal overload protectors.
If field replacement of a blower motor is necessary, most blower assemblies, including the mounting
plate, are readily removable. Each of the blower mounting plates is held to the air conditioner cabinet
structure by screws and nuts. For installation of the replacement blower, electrical connections may
be broken at the terminal block, or power leads may be cut and appropriately spliced together. 

Do not operate the air conditioner for extended periods of time with the filter removed.

The condenser coil may become clogged with dust or lint from the air entering the face.

A clogged condenser coil is not readily detected and will give the same reaction as a

clogged filter. A clean filter is the best protection.

Содержание Advantage RT Top Mount Series

Страница 1: ...THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 037 03 1 19 CDR 20131 ADVANTAGE...

Страница 2: ...ic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtua...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE...

Страница 5: ...by the compressed refrigerant to the condenser coil Ambient air is then passed through the condenser coil where it absorbs the heat and is then discharged to the environment This unit is equipped wit...

Страница 6: ...no unusual noise or vibration should be evident Both the evaporator and condenser fans or blowers should be delivering air through their respective discharge ports The cool air discharged should be le...

Страница 7: ...trength mounting screws are recommended The external drain hose must not be elevated above the exit port Improper mounting will impede the flow of condensate and may cause internal malfunctions CAUTIO...

Страница 8: ...7 2 13 38 340 0 1 90 48 2 9 00 228 6 TYP 12 00 304 8 3 70 94 0 2 59 54 8 6 00 152 4 6 00 152 4 14 12 358 6 2 50 63 5 2 83 72 0 Drawings and Dimensions KA__C__RTL Dimensions inches metric are for refer...

Страница 9: ...87 0261 287 0261 287 Condenser Blower Capacitor 0452 03 0452 03 0452 03 0452 03 0452 03 Evaporator Blower Motor 0265 03 0194 76 0194 14 0194 76 0194 14 Evaporator Blower Capacitor N A 0452 65 0452 65...

Страница 10: ...ners feature an easily removable inlet filter to facilitate necessary cleaning To access the filter loosen the torx screws and remove the front grille Push the filter upward and pull the bottom edge f...

Страница 11: ...need for replenishment of refrigerant charge When it has been verified by a Certified EPA Technician that a refrigerant shortage does exist the leak must be repaired Then the unit may be evacuated and...

Страница 12: ...essor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: