background image

5

Drawings and Dimensions

  (8) .281 

   [7.0] DIA. 

HOLES

10.00

 [254.0]

UNIT
OUTLINE

8.97

 [227.8]

12.00

 [304.8]

 7.07

 [179.5]

9.62

[244.3]

TYP.

1.87

 [47.4]

 1.00

 [25.4]

 1.51

 [38.3]

 1.66

 [42.1]

 8.05

 [204.4]

 13.82

 [351.0]

 33.00

 [838.2]

 7.10

 [180.3]

  10.68
 [271.2]

  12.00
 [304.8]

  33.00
 [838.2]

AMBIENT 

AIR OUT

ENCLOSURE 

AIR IN

ENCLOSURE

AIR OUT

M/TAB

AMBIENT 

AIR IN

AMBIENT 

AIR OUT

Dimensions, inches [mm], are for reference only and are subject to change.

KXRP33

Technical Data*

Maximum Allowable

Temperature °F

Approx.

Power

Enclosure

Ambient

Watts/°F

Weight

Model

Volts Amps Watts

Max

Min/Max

Air In

(lbs.)

KXRP33

115

2.25

260

160

-20/131

30

48

K2XRP33

230

1.00

225

160

-20/131

30

48

*

60 Hz operation. For 50 Hz operation consult Kooltronic

Major Component Replacements

Heat Exchanger

Model

Impeller

Capacitor

Filter

Element

KXRP33

0194-14

0452-06

7131F

210033-00-26GLV

K2XRP33

0194-15

0452-73

7131F

210033-00-26GLV

Mounting Plan

NOTE: Part Numbers shown are for 60Hz/1Ø. For 50Hz consult Kooltronic.

Содержание Advantage KXRP33

Страница 1: ...S HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 17 7 19 CDR 20178 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...nic Advantage Heat Exchangers are designed for outdoor and indoor applications with ambient temperature from 20 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general infor...

Страница 3: ...read and thoroughly understand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Model Number Serial Number Electrical power characteristics Maximum enclosure temperature Filter Part Number We recommend you copy this information from your unit 3 CAUTION Operate this unit only on the proper voltages ...

Страница 4: ... TAB orientation Place the M TAB flush against the outside of the enclosure to locate cutouts and mounting holes 3 Mount the M TAB to the outside of the cabinet using all the mounting hardware supplied by Kooltronic 1 4 20 screws nuts washers NOTE Make sure the screws are inserted with heads on the M TAB side 4 Route the power cord through the bottom cut out in your cabinet Mount the unit to the M...

Страница 5: ...nce only and are subject to change KXRP33 Technical Data Maximum Allowable Temperature F Approx Power Enclosure Ambient Watts F Weight Model Volts Amps Watts Max Min Max Air In lbs KXRP33 115 2 25 260 160 20 131 30 48 K2XRP33 230 1 00 225 160 20 131 30 48 60 Hz operation For 50 Hz operation consult Kooltronic Major Component Replacements Heat Exchanger Model Impeller Capacitor Filter Element KXRP3...

Страница 6: ...lso available from Kooltronic If filter service is neglected or delayed the heat exchanger will not perform at its design capacity The first indication of an excessively clogged air filter is a gradual increase of temperature within the equipment cabinet Continued operation under these conditions may cause damage shorten blower motor life and void the warranty Heat Exchanger Element Cleaning 1 Loo...

Страница 7: ...nded periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element will cause a gradual increase of temperature within the equipment cabinet A clean filter is the best protection VIII Packing Procedure Keep Heat Exchanger in proper upright position Pack Heat Exchanger in an appropriate carton pr...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: