background image

II. Incoming Inspection

Kooltronic Heat Exchangers are designed, built, and packaged to withstand the shock and vibration normally
associated with shipment by common carriers. Occasionally improper handling during shipping causes damage.
Such handling could include unbanding of palletized shipments, failing to respect any carton handling
instructions, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be
done upon receipt of all shipments. Any carton tears, dents, scratches, or loose articles should be noted on the
Freight Bill. Cartons should be opened promptly and the units inspected for CONCEALED DAMAGE.

An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing
materials. Kooltronic cannot assume responsibility for Consignee’s failure to file a timely freight claim.

III. Product Handling

Do not attempt to operate your Kooltronic Heat Exchanger until you read and thoroughly 
understand this Manual.

Before operating this unit, all electrical wiring must be checked to assure the proper connections.

IV. Product Identification and Nameplate

Model Number

Serial Number

Electrical power characteristics

Maximum enclosure temperature

Filter Part Number

We recommend you copy this information 
from your unit.

3

CAUTION

Operate this unit only on the proper voltages and frequencies as 

noted on the nameplate.

MODEL NO.

SERIAL NO.

MAX. CABINET

VOLTS.

FREQ.

PH.

AMPS

TEMP. 

o

F

MAX.

FILTER P/N

FUSE SIZE

UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY

ALL MOTORS ARE THERMALLY PROTECTED

THIS PRODUCT IS PROTECTED BY ONE OR MORE OF THE FOLLOWING
PATENTS: 3,019,965  3,120,166  3,211,360  3,559,728  3,807,493  AND 
OTHER PATENTS PENDING

MANUFACTURED BY:

KOOLTRONIC, INC.  PENNINGTON, NJ

Heat Exchanger

     

When ordering parts, specify the
Model Number and Serial Number.

Make sure that these parameters are
met. Failure to do so may result in
permanent damage to the unit.

Before operating, be sure that the
power source matches these
requirements.

  

Each Kooltronic Heat Exchanger includes an identification nameplate. This nameplate provides:

Содержание Advantage KXRP33

Страница 1: ...S HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 17 7 19 CDR 20178 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...nic Advantage Heat Exchangers are designed for outdoor and indoor applications with ambient temperature from 20 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general infor...

Страница 3: ...read and thoroughly understand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Model Number Serial Number Electrical power characteristics Maximum enclosure temperature Filter Part Number We recommend you copy this information from your unit 3 CAUTION Operate this unit only on the proper voltages ...

Страница 4: ... TAB orientation Place the M TAB flush against the outside of the enclosure to locate cutouts and mounting holes 3 Mount the M TAB to the outside of the cabinet using all the mounting hardware supplied by Kooltronic 1 4 20 screws nuts washers NOTE Make sure the screws are inserted with heads on the M TAB side 4 Route the power cord through the bottom cut out in your cabinet Mount the unit to the M...

Страница 5: ...nce only and are subject to change KXRP33 Technical Data Maximum Allowable Temperature F Approx Power Enclosure Ambient Watts F Weight Model Volts Amps Watts Max Min Max Air In lbs KXRP33 115 2 25 260 160 20 131 30 48 K2XRP33 230 1 00 225 160 20 131 30 48 60 Hz operation For 50 Hz operation consult Kooltronic Major Component Replacements Heat Exchanger Model Impeller Capacitor Filter Element KXRP3...

Страница 6: ...lso available from Kooltronic If filter service is neglected or delayed the heat exchanger will not perform at its design capacity The first indication of an excessively clogged air filter is a gradual increase of temperature within the equipment cabinet Continued operation under these conditions may cause damage shorten blower motor life and void the warranty Heat Exchanger Element Cleaning 1 Loo...

Страница 7: ...nded periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element will cause a gradual increase of temperature within the equipment cabinet A clean filter is the best protection VIII Packing Procedure Keep Heat Exchanger in proper upright position Pack Heat Exchanger in an appropriate carton pr...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: