background image

4

V. Principles of Operation

VI.

Specific Model Data

Mounting

ENCLOSURE 

HEATED AIR IN

ENCLOSURE 

COOLED AIR OUT

ELECTRICAL 

HEATER

AMBIENT 

AIR IN

AMBIENT 

AIR OUT

AMBIENT 

BLOWER

HEAT 

EXCHANGER

ELEMENT

ENCLOSURE 

BLOWER

The heater option includes the electrical heater, ambient blower,
bimetal thermostat, heater thermostat and limiter thermostat. All of the
thermostats are installed in the discharged enclosure air stream. When
the enclosure discharge air goes below 70°F, the ambient blower
thermostat shuts off the ambient blower.  When the enclosure
discharge air goes above 85°F, the ambient blower thermostat turns
on the ambient blower.

When discharge enclosure air goes below 40°F, the heater
thermostat turns on the heater. When the discharge enclosure air
goes above 60°F, the heater thermostat shuts off the heater. See
wiring diagram on page 6.

1.

Loosen the two screws on the bottom of the unit.

2.

See Drawings and Dimensions for proper M/TAB orientation. Place the M/TAB flush against the
outside of the enclosure to locate cutouts and mounting holes.

3.

Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by
Kooltronic (

1/4 

-20 screws/nuts/washers). NOTE: Make sure the screws are inserted with heads

on the M/TAB side.

4.

Route the power cord through the bottom cut out in your cabinet. Mount the unit to the M/TAB
by sliding the slots on each side panel into the hooks on the M/TAB.

5.

Tighten the two screws on the bottom of the unit and seal against the enclosure.

The main component of the heat exchanger is the counterflow aluminum element through which the heat
transfer occurs.

Ambient blower draws ambient air from the bottom inlet through an aluminum mesh air filter, and the
element, and exhausts it through a discharge grill.

Cabinet blower draws cabinet air from the top inlet, blows it through the element and exhausts it through
the bottom discharge into the cabinet.

Kooltronic Heat Exchangers have been engineered to be installed easily. To avoid damaging your
Heat Exchanger, please read the following information before installation:

Содержание Advantage KXRP33

Страница 1: ...S HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 17 7 19 CDR 20178 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...nic Advantage Heat Exchangers are designed for outdoor and indoor applications with ambient temperature from 20 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general infor...

Страница 3: ...read and thoroughly understand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Model Number Serial Number Electrical power characteristics Maximum enclosure temperature Filter Part Number We recommend you copy this information from your unit 3 CAUTION Operate this unit only on the proper voltages ...

Страница 4: ... TAB orientation Place the M TAB flush against the outside of the enclosure to locate cutouts and mounting holes 3 Mount the M TAB to the outside of the cabinet using all the mounting hardware supplied by Kooltronic 1 4 20 screws nuts washers NOTE Make sure the screws are inserted with heads on the M TAB side 4 Route the power cord through the bottom cut out in your cabinet Mount the unit to the M...

Страница 5: ...nce only and are subject to change KXRP33 Technical Data Maximum Allowable Temperature F Approx Power Enclosure Ambient Watts F Weight Model Volts Amps Watts Max Min Max Air In lbs KXRP33 115 2 25 260 160 20 131 30 48 K2XRP33 230 1 00 225 160 20 131 30 48 60 Hz operation For 50 Hz operation consult Kooltronic Major Component Replacements Heat Exchanger Model Impeller Capacitor Filter Element KXRP3...

Страница 6: ...lso available from Kooltronic If filter service is neglected or delayed the heat exchanger will not perform at its design capacity The first indication of an excessively clogged air filter is a gradual increase of temperature within the equipment cabinet Continued operation under these conditions may cause damage shorten blower motor life and void the warranty Heat Exchanger Element Cleaning 1 Loo...

Страница 7: ...nded periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element will cause a gradual increase of temperature within the equipment cabinet A clean filter is the best protection VIII Packing Procedure Keep Heat Exchanger in proper upright position Pack Heat Exchanger in an appropriate carton pr...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: