WAKL5N0802A
Edition: 07.02.2022
Page: 15/18
4.6. Check the control
See the original instructions of the control!
5. Repair instructions for UL500 EM/ UL700 EM
Because of its modular design the air conditioner UL500 EM / UL700 EM features a series of char-
acteristics in mounting and demounting of the components.
5.1.
Demounting and mounting of evaporator blowers
Loosen the quick fasteners and
open the evaporator cover /hoods
and secure them against falling.
The blower is furnished with an insert (blower plate) that is fitted into the bottom part of the unit.
5.1.1. Demounting evaporator blowers
Remove the blower with the insert (blower plate) from the
bracket on the side facing the evaporator heat exchanger, as
shown by the arrow.
Disconnect the cable and replace it, if necessary.
Blower plate
Danger! Risk of injury!
Make sure that the device is turned off!
There is a risk of injuries caused by rotating parts (blower)