110013961AA
date of change: 18.08.2008
page: 17/19
Group
]
FAn
(parameter concerning control of cooling fans)
[refers to Pr2]
Par.
Description
Ran-
ge
Def.
COOL
cooling
hot-gas
defrost-
ing
COOL
cooling
recircu-
lated air
defrost-
ting
nr
cooling
neutral
zone
heating
hot-gas
defrost-
ing
nr
cooling
neutral zone
heating
recirculated
air defrosting
FCO
F
Fan state concerning to
control cycle
- temperature Pr2 beyond „fan line“
fans (Fan) always off
- temperature within “fan line”
ON = fan always on
OFF= fan / compressor connected
(compressor on / fan on)
(compressor off / fan off)
On -
OFF
On
On
On
On
On
FEdF
Fan state concerning to
defrost cycle
- temperature Pr2 beyond „fan line“
fan (Fan) always off
- temperature within „fan line“
ON = FAn / dEF connected
(dEF on / FAn on)
(dEF off / FAn off)
OFF = fan (FAn) always off
Only visible if defrosting mode dtyP = „EL“ or „in“
If defrosting mode is dtyP = FdE, then it is hidden
And fan (Fan) always on
On -
OFF
OFF
OFF
----
OFF
----
FLt
Top limit temperature fan
(if temperature Pr2 is higher than adjusted value
FLt, then fan is off)
(upper limit „fan line“, consider FLt > Fct)
- 58 ÷
302
°C/°F
50.0
50.0
50.0
50.0
50.0
Fct
Lower limit temperature fan
(if temperature Pr2 is lower than the adjusted value
Fct, then fan is off)
(lower limit „fan line“, consider Fct < FLt)
- 58 ÷
302
°C/°F
-50.0
-50.0
-50.0
-50.0
-50.0
dF
Switch difference fan lock
(hysteresis for outlet FAn)
0 ÷
30
°C/°F
2.0
2.0
2.0
2.0
2.0
Fd
Fan delay after defrost cycle
(switch-on delay outlet Fan after defrosting)
OFF
÷
99.59
min.s
ec
2
2
OFF
2
OFF
d F
d F
tim e
F A n
o ff
O N
F c t
P r2
T e m p .
F L t
o ff
o ff
O N